Capacities and Selection Data
Floating Air Pro / Premier Cooling Extended Capacity (By System Model)
System Model
FPHW363/A/B
FRHW093/A
FPHW123/A
15
SPECIFICATIONS
Outdoor Air
Temp. (°F DB)
32
41
50
59
67
77
82
87
95
104
115
32
41
50
59
67
77
82
87
95
104
115
32
41
50
59
67
77
82
87
95
104
115
Indoor Air Temp. °F DB / °F WB
Cooling BTUs
Heating BTUs
kBtu/h
29.25
32.72
33.50
33.88
35.27
36.36
37.89
37.20
32.91
29.64
23.63
7.60
8.41
9.73
11.23
12.94
14.12
14.48
14.27
13.56
12.67
11.62
13.76
14.12
14.60
14.92
15.38
15.50
15.89
15.73
15.19
14.44
13.31
80 /67
Power
20.48
22.90
23.45
23.72
24.69
25.45
26.52
26.04
23.04
20.75
16.54
5.32
5.89
6.81
7.86
9.06
9.89
10.13
9.99
9.49
8.87
8.13
9.63
9.88
10.22
10.44
10.77
10.85
11.12
11.01
10.64
10.11
9.32
kW
1.09
1.45
2.20
2.46
2.63
3.52
3.59
3.69
3.90
3.65
3.13
0.21
0.28
0.40
0.50
0.69
0.89
1.04
1.07
1.16
1.25
1.40
0.33
0.47
0.50
0.70
0.84
1.09
1.15
1.17
1.27
1.38
1.32

Hide quick links: