PROGRAMMING
This chapter describes the programming of the multiple input module.
8.1

Precautions for Programming

This section describes precautions to create CC-Link IE Field Network programs.
Cyclic transmission program
For a cyclic transmission program, interlock with the following link special relay (SB) and link special register (SW).
• Own station data link status (master station) (SB0049)
• Data link status (each station) (SW00B0 to SW00B7)
For details on the link special relay (SB) and link special register (SW), refer to the user's manual for the master/local module
used.
Ex.
Interlock example
(1)
(2)
(1)Communication program with station No.1
(2)Communication program with station No.2
Transient transmission program
For a transient transmission program, interlock with the following link special relay (SB) and link special register (SW).
• Own station baton pass status (master station) (SB0047)
• Baton pass status (each station) (SW00A0 to SW00A7)
For details on the link special relay (SB) and link special register (SW), refer to the user's manual for the master/local module
used.
Ex.
Interlock example
(1)
(1)Start contact
(2)Dedicated instructions to station No.1