Trial Operation and Testing

• Before starting the trial operation, measure the voltage at the primary side of the circuit breaker.
• Check that all liquid and gas stop valves are fully open.
• Check that piping and wiring all match. The wiring error check can be conveniently used for underground wiring and other wiring
that cannot be directly checked. However, if the outside air temperature is
will not operate.
• When trial operation is conducted directly after the circuit breaker is turned on, in some cases no air will be output for about 15
minutes in order to protect the air conditioner.
1.

Wiring error check

This product is capable of automatic correction of wiring errors.
Press the wiring error check switch on the outdoor unit service PC-board. However, the
wiring error check switch will not function for 3 minutes after the safety breaker is turned
on. About 15-20 minutes after the switch is pressed, the errors in the connection wiring
will be corrected.
The service monitor LEDs indicate whether or not correction is possible, as
shown in the table below. For details on how to read the LED display, refer to
the collective indications label on the reverse side of the top plate or the service
manual.
If self-correction is not possible, check the indoor unit wiring and piping in the usual
manner.
LED
1
2
All
Status
Flashing
(One or more of LEDs 1 to 4 are ON)
Wiring correct example
Terminal block
From Room C
to the "kitchen"
NOTE
1) For two rooms, LED 3,4 and 5 are not displayed, and for three rooms, LED 4 and 5 is not displayed, and for four rooms,
LED 5 is not displayed.
2) After wiring error check operation is completed, LED indication will continue until ordinary operation starts. This is normal.
3) Follow the product diagnosis procedures. (Details of product error diagnosis are listed on the reverse side of the top plate.)
17
3
4
Flashing
Automatic correction impossible
One after another
Automatic correction completed
Abnormal stop [Note. 3]
From Room B
From Room D
to the "living room"
to the "children's room"
LED lighting sequence after a wiring correction.
Order of LED flashing: 2
41°F (5°C) or less
Message
The figure at left shows branch wiring.
From Room A
to the "bedroom"
Wiring error check
1
3
4
, the wiring error check function
Service PC-board
A
1
2
3
4
5
Wiring error
check switch
(SW3)