Insulating The Refrigerant Piping And Connections - Trane 22 Series Installer's Manual

Multi-zone inverter system
Table of Contents

Advertisement

4. Do not bend the pipe while insulated. First, cut the insulation with a sharp cutting tool and
expose it to the appropriate bend radius, as shown below. After bending the pipe, replace the
insulation and seal it with pipe wrap tape.
1. To prevent distortion and breaking of the pipe, bend the pipe with a radius of curvature of 6 in.
(150 mm) or more. Use a tubing bender when forming the copper tubing into a bend.
2. If the pipe is bent repeatedly at the same place, it will break.
Connect the gas pipe after connecting the liquid pipe completely.

Insulating the Refrigerant Piping and Connections

1. The refrigerant pipes should be insulated and wrapped with appropriate insulating
material and wrapping tape. This will prevent condensation, water leakage and
damage to the insulating material.
2. The connections at the indoor unit should be wrapped with insulating material. No
gap is allowed on the joint of the indoor unit, as shown below.
22 Series Multi-Zone
NOTICE
CAUTION