CGa Series 3 Gas-Fired Water Boiler — Boiler Manual
6d
Start-up — verify operation
Check burner flames
Pilot burner flame (
PROPER pilot flame
1. Blue flame.
2. Inner cone engulfing pilot flame sensor (spark-
ignited pilot).
3. Pilot flame sensor glowing cherry red.
IMPROPER pilot flame
1. Overfired — Large flame lifting or blowing past pilot
flame sensor.
2. Underfired — Small flame. Inner cone not engulfing
pilot flame sensor.
3. Lack of primary air — Yellow flame tip.
Main burner flame (
PROPER main burner flame
1. Yellow-orange streaks may appear (caused by dust).
IMPROPER main burner flame:
1. Overfired — Large flames.
2. Underfired — Small flames.
3. Lack of primary air — Yellow tipping on flames
(sooting will occur).
Check vent damper operation
Raise room thermostat to call for heat
1.
damper actuator will slowly open vent damper.
When vent damper is fully open
2.
then allow main burners to ignite.
Lower thermostat setting
3.
will go out, then vent damper will close.
Repeat Steps 2 through 4
4.
operation.
32
Section 9
See
for operation and operating information.
Figure 21
)
Figure 22
)
— Vent
— Pilot will light,
Vent damper must be fully open
before main burners light. If vent
damper does not fully open, flue
products such as carbon monoxide
will escape into house, causing se-
vere personal injury or death.
— Main burner flames
several times to verify
Figure 21 Typical pilot burner flame
Figure 22 Typical main burner flame
5. Return thermostat to normal setting.
6. Set thermostat heat anticipator setting indicated on
wiring diagram.
Check vent system operation
1. Check vent system at least once a month during
heating season. With boiler firing, hold candle or
match below lower edge of draft hood "skirt". If
flame does not blow out, but burns undisturbed,
vent system is functioning properly. If flame blows
out or flickers drastically, inspect vent system for
obstructions or other causes of improper venting
(such as exhaust fans in boiler room).