8-6. Low outdoor temperature protection

When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode
Trigger condition
Release condition

8-7. High temperature and high pressure release control

The compressor is controlled as follows.
Indoor unit heat exchanger
temperature rises
Zone A
AB
Zone B
BC
Zone C
CD
Zone D
Zone E
Zone
Zone A
Compressor is stopped.
Zone B
The rotation number of compressor is decreased.
Zone C
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-6. Low outdoor temperature protection
Indoor unit heat exchanger
temperature drops
Stable zone
DE
- (04-31) -
Cooling/Dry
5°F (-15°C)
14°F (-10°C)
AB:
145.4°F (63°C)
BC:
131.0°F (55°C)
CD:
127.4°F (53°C)
DE:
122.0°F (50°C)
Operation
-25 rps/120 sec.
-3 rps/60 sec.
8. Various protections