Specifications; Valve Installation - Emerson Fisher Design GX Series Instruction Manual

Control valve and actuator system
Table of Contents

Advertisement

GX Valve and Actuator

Specifications

Valve Body Size
Pressure Rating
End Connections
Valve Body/Bonnet
Materials
Face-to-Face Dimensions
Shutoff per IEC 60534-4
and ANSI/FCI 70-2
Flow Direction
Flow Control
Characteristics
Trim Style
Travel Stop
1. For 4.8 to 14 mm ports, Class VI shutoff is achieved without PTFE seat.

Valve Installation

WARNING
Always wear protective gloves,
clothing, and eyewear when
performing any installation operations
to avoid personal injury.
Personal injury or equipment damage
caused by sudden release of pressure
or bursting of pressure retaining parts
might result if service conditions
exceed those for which the product
was intended. To avoid injury or
damage, provide a relief valve for over
pressure protection as required by
government or accepted industry
codes and good engineering practices.
Check with your process or safety
engineer for any additional measures
that must be taken to protect against
process media.
If installing into an existing
application, also refer to the WARNING
at the beginning of the Maintenance
section in this instruction manual.
2
All manuals and user guides at all-guides.com
Table 1. Design GX Valve Specifications
EN
DN 15, 20, 25, 40, 50, 80, 100, 150
PN 10 / 16 / 25 / 40 per EN 1092-1
Flanged raised face per EN 1092-1
1.0619 steel
1.4409 stainless steel
CW2M (sizes DN 25 through DN 100 only)
Consistent with EN 558-1
Port Diameters
4.8 mm
Micro-Flow trim (unbalanced)
9.5, 14, 22 mm
Stem-Guided with Contoured Plug (unbalanced)
36, 46 mm
Port-Guided Plug (unbalanced)
Balanced Trim with Contoured plug (standard) or Unbalanced
70, 90, 136 mm
Port-Guided Plug (optional)
0.5, 0.75, 1, 1.5, 2, 3, 4, 6-inch
Class 150 / 300 per ASME B16.34
Flanged raised face per ASME B16.5
ASME SA216 WCC steel
ASME SA351 CF3M stainless steel
CW2M (sizes 1- through 4-inch only)
Consistent with EN 558-2 (same as ISA S75.03)
Metal seat - Class IV (standard)
Metal seat - Class V (optional)
PTFE seat - Class VI (optional)
Flow-up only
Equal Percentage and Linear
Trim Style Description
Available as an option
This valve is intended for a specific
range of pressures, temperatures and
other application specifications.
Applying different pressure and
temperatures to the valve could result
in parts damage, malfunction of the
control valve or loss of control of the
process. Do not expose this product to
service conditions or variables other
than those for which the product was
intended. If you are not sure what
these conditions are you should
contact your Emerson Process
Management sales office for more
complete specifications. Provide the
product serial number (shown on the
nameplate, figure 2) and all other
pertinent information.
If you move or work on an actuator
installed on a valve with loading
pressure applied, keep your hands and
tools away from the stem travel path to
avoid personal injury. Be especially
Instruction Manual
Form 5770
June 2006
ASME
(1)
CAUTION
WARNING

Advertisement

Table of Contents
loading

Table of Contents