40MAHB: Service Manual
DIAGNOSIS AND SOLUTION (CONT)
Remarks:
• Use a multimeter to test the DC voltage between the 2 port (or S or L2 port) and 3 port (or N or S port) of the outdoor unit.
• The red pin of multimeter connects with 2 port (or S or L2 port) while the black pin is for 3 port (or N or S port) the unit is running normal, the
voltage is moving alternately as positive values and negative values.
• If the outdoor unit malfunctions, the voltage remains in a narrow positive value.
• If the indoor unit malfunctions, the voltage maintains a fixed value.
• Use a multimeter to test the reactor's resistance which does not connect with capacitor.
• The normal value should be around zero ohm. Otherwise, the reactor has malfunctioned. Check the reactor and make sure it is not shorted to the
ground.