Overview; Specifications; General Specifications - Mitsubishi CL2XY16-DTP1C5V User Manual

Table of Contents

Advertisement

1. Overview

This user's manual explains specifications and names of individual parts of the
CL2XY16-DTP1C5V type CC-Link/LT remote I/O module (hereinafter
abbreviated as remote I/O module).

2. Specifications

2.1 General Specifications

The General specifications for the remote I/O module are shown in the following
table.
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration
resistance
B 3502, IEC
Shock resistance
Operating
ambience
Operating altitude
Installation location
Overvoltage
category *1
Pollution level *2
*1: This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery
within premises. Category II applies to equipment for which electrical power is supplied
from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*2: This index indicates the degree to which conductive material is generated in terms of the
environment in which the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity
caused by condensing must be expected occasionally.
*3: It can also be used in an environment other than on the control panel if the conditions such
as usage ambient temperature and humidity are satisfied.
Under
Conforming
intermittent
to JIS
vibration
61131-2
Under
continuous
vibration
IEC 61131-2 (147 m/s
Specifications
0 to 55
-25 to 75
5 to 95%RH, non-condensing
5 to 95%RH, non-condensing
Frequency
Acceleration
10 to 57Hz
———
9.8m/s
57 to 150Hz
10 to 57Hz
———
4.9m/s
57 to 150Hz
Conforming to JIS B 3502,
2
, 3 times in each of 3 directions X, Y, Z)
No corrosive gases
2000m (6562ft.) max.
Inside control panel *3
II max.
2 max.
1
Sweep
Amplitude
count
0.075mm
10 times
(0.003in.)
each in
2
———
X, Y, Z
directions
0.035mm
(for 80
(0.001in.)
min.)
2
———

Advertisement