Additional Configuration

Further configuration is now possible to allow personalisation of your SMS Lite.
You can assign a site name as well as naming each of the inputs and outputs and assigning phone(s)
to these. The SMS Lite can be configured with up to 4 phone numbers allowing multiple user
notifications and control options.
Tip – A configuration worksheet can be found at the back of this manual and on our website.
We highly recommend these are used to record the Site, I/O names, phone numbers and their escalation order.

Naming Conventions

Before renaming the site name, inputs, and outputs there are important considerations and
limitations.
Use alphanumeric characters – only use letters A to Z and numbers 1 to 9
Do NOT use spaces in the names – eg do not use "VSD RUN" or "PUMP SHED"
Do NOT use names longer than 8 characters – keep them short, 4 characters is recommended
Do NOT use punctuation marks or special characters: Do not use <: ; . , ? / @ # emojis etc
Do NOT use reserved keywords in the name. These includes ON, OFF, NAME, PHONE, SITE,
DEBOUNCE, DEFAULTS, OK, BUSY, PULSE, STATUS, BAL, STATS, INFO, INPUTS, OUTPUTS
Do NOT duplicate names, each name must be unique.

Additional Phone Numbers

Configure up to 3 additional users to allow notification and control options, using the same process
used to configure the Ph1 Master user.
1. Compose text message to the SMS Lite mobile number in the following format:
#[PIN][space]Ph2:number=0124567890[dot] (e.g. #12345 Ph2:number=022987654.)
2. A confirmation text will be sent to you acknowledging a configuration change.

Configuration Options

All configuration text messages sent to the SMS Lite must in the form of:
#[PIN][space]<object>:<item>=<value>[dot]
e.g.
#12345 Site:Name=Shed1.
Or
#12345 INP1:Name=Pump.
Configuration options are shown in the following table:
Object
Site
INP1, INP2, INP3, INP4
These are the 4 individually
configurable inputs
SMS Lite 4G– User Guide
Item
Name
Name
Phones
© 2022 QTech Data Systems Ltd
Value
Name of the site where the SMS Lite is.
(8-character limit, no spaces)
An identifying name for the input.
(8-character limit, no spaces)
Ph1→Ph4
Which configured phone number(s) will
receive notifications from this input.