36
The operating temperatures of the relay are recommended to be set, typically for
example, as follows:
• 120...140 °C when only tripping is in use
• alarm 120...140 °C and trip 130...150 °C when both alarm and trip are used.

ATEX certified thermal protection with PTC (+L513)

The option contains an ATEX certified thermistor relay.

Description

In combination with safety option +Q950, the option provides the ATEX certified
thermal motor protection function of the drive.
More information: See ATEX Certified Thermal Motor Protection Function User's
Manual (3AFE68401941 [English]).