Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Height
Lateral
H
L
(feet)
(feet)
0
2
6
4
6
0
2
8
5
8
0
2
10
5
10
0
2
5
15
10
15
0
2
5
20
10
15
20
0
2
5
10
30
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-
mum listed capacity).
Serving a Single Category I Appliance
3 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MIN
MAX
MIN
0
78
13
51
18
21
49
30
25
46
36
0
84
12
57
16
23
53
32
28
49
39
0
88
12
61
17
23
57
32
30
51
41
0
94
11
69
15
22
65
30
29
59
40
35
53
48
0
97
10
75
14
21
71
29
28
64
38
34
58
46
48
52
55
0
100
9
81
13
21
77
28
27
70
37
33
64
44
56
58
53
NR
NR
73
TABLE 3
Vent and Connector Diameter − D (inches)
4 Inch
MAX
MIN
0
152
0
97
27
94
39
91
47
0
165
0
109
25
103
42
98
51
0
175
0
118
23
113
41
104
54
0
191
0
136
20
130
39
121
51
112
61
0
202
0
149
18
143
38
133
50
124
59
116
69
0
213
0
166
14
160
36
150
48
141
57
132
66
113
88
Page 18
5 Inch
6 Inch
MAX
MIN
251
0
157
32
153
50
149
59
276
0
178
28
171
53
164
64
295
0
194
26
187
52
176
67
327
0
226
22
219
49
206
64
195
76
349
0
250
20
242
47
229
62
217
73
206
84
374
0
283
18
275
45
262
59
249
70
237
80
214
104
MAX
375
232
227
223
415
263
255
247
447
289
280
267
502
339
330
315
301
540
377
367
351
337
322
587
432
421
405
389
374
346