Navien NCB700-2S Plus 42K Installation & Operation Manual page 48

Condensing combi boiler
Table of Contents

Advertisement

A terminal must not be sited under a car port roof.
Note
In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where this
may cause a nuisance, i.e. positions A, D, G, H, J or M.
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
A terminal must not be sited below 2 m where people have access to, such as public footpaths, access routes, patios etc.
However, If the terminal is fitted less than 2 m above a surface where there is no public access, the terminal must be protected
by a terminal guard.
Proximity of Flue Duct Outlet to a Boundary
3
a) Facing the boundary
3
c) At an angle to the boundary
#
Description
1
Boundary
2
Terminal
3
Building
4
Adjacent building
5
Window
48
Flue System
2
3
1
4
2
3
b) Parallel to the boundary
5
d) Opening in adjacent building
2
1
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ncb700-3s 54k

Table of Contents