17
Electronic control function
17.1 Abbreviation
For AG:
T1: Indoor room temperature
T2: Coil temperature of evaporator
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
Tp: Compressor discharge temperature
Tsc: Ajusted setting temperature
For other models:
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet(This sensor is located in outdoor unit)
T3: Coil temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Setting temperature
17.2 Electric control working environment.
1. Input voltage: 198V~264V.
2. Input power frequency:50Hz.
3. Indoor fan normal working amp. is less than 1A.
4. Outdoor fan. normal working amp. is less than 1.5A.
5. Four-way valve normal working amp. is less than 1A.
17.3 Outdoor unit's digital display tube
There is a digital display tube in outdoor PCB.
Digital display tube display function
In standby , the LED displays "- -"
In compressor operation, the LED display the running frequency,
In defrosting mode, The LED displays "dF" or alternative displays between running frequency and
"dF"(each displays 0.5s)
In compressor pre-heating, The LED displays "PH" or alternative displays between running frequency
and "PH"(each displays 0.5s)
During the oil return process, The LED displays "RO" or alternative displays between running
frequency and "RO"(each displays 0.5s)
In low ambient cooling mode, the LED displays "LC" or alternative displays between running
73