Routine Servicing - Navien NCB300-28K Installation & Operation Manual

Condensing combi boiler
Hide thumbs Also See for NCB300-28K:
Table of Contents

Advertisement

If hot water will not flow and you suspect that the boiler is
frozen, follow these steps:
1. Press the Power button (
the boiler.
2. Close the gas valve.
Gas Valve
3. Open the hot water tap that is closest to the boiler.
4. Use a hair dryer or a portable electric heater to heat up both
the primary and secondary heat exchangers.
5. Check every few minutes to see if water is running at the
open tap.
6. When the water starts flowing again, check the boiler and
piping for leaks. If you detect any leaks or the boiler is not
operating properly, contact an authorised technician or
licensed professional.
This boiler requires very little maintenance, however
Note
a qualified technician should inspect the boiler at the
beginning of every heating season and/or when there
is a problem.
60
Maintaining the Boiler
) on the front panel to turn off
Opened
Closed

11.5 Routine Servicing

Navien advises on an interim service inspection with a flue gas
analyser. A full strip down service is recommended at regular
intervals or where analyser readings are not within correct safety
standards.
11.5.1 Interim Service
For reasons of safety and economy, it is recommended that the
boiler is serviced annually. Servicing must be performed by a
competent person in accordance with BS 7967. After servicing,
complete the relevant Service Interval Record section of the
Benchmark Checklist located on the inside back page of this
document.
Service technician (See the following instructions)
General:
Address reported problems
Inspect interior; clean and vacuum if necessary
Clean condensate trap and fill with fresh water
Check for leaks (water, gas, flue, condensate)
Verify flue and air lines are in good condition and
sealed tight
Check system piping
Check control settings
Annual
Check ignition and flame rod (clean and
Start-up
reposition)
Check wiring and connections
Flame inspection (stable, uniform)
Flame signal
Remove and clean return adapter filter
Servicing of the in-line magnetite filter
Check system inhibitor concentration and
appropriate action taken, in accordance with BS
7593