Single pole (one location) or 3-way (multi-location) electronic low-voltage dimmer (lighted)

Advertisement

Quick Links

PK-93606-10-00-0A-X0
WARNINGS AND CAUTIONS:
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult a qualified electrician.
• To avoid overheating and possible damage to this device and other equipment, do not install to control a receptacle, fluorescent lighting, a motor- or a transformer-operated appliance.
• Use with electronic low-voltage transformers only. Do Not use to control a magnetic low-voltage transformer. Use a Leviton magnetic low-voltage dimmer to control magnetic
low-voltage transformers.
• This dimmer provides protection from overheating. An excessive load applied to the dimmer will cause the dimmer to overheat. The excess load must be removed to resume proper operation.
• Acenti™ dimmers are not compatible with standard 3-way or 4-way switches. They must be used with compatible Acenti™ remotes for multi-location dimming.
• Use only one (1) Acenti™ dimmer in a multi-location circuit with up to 9 coordinating remotes without LEDs or up to 4 matching remotes with LEDs. The remote(s) will turn the light on at the
brightness level selected at the dimmer.
Tools needed to install your Dimmer
Slotted/Phillips Screwdriver
Electrical Tape
Pliers
Pencil
Cutters
Ruler
Installing Dimmer by itself or with other devices
If installing Dimmer in a single device application, proceed with the
INSTALLING YOUR DIMMER section. If installing Dimmer in a
multi-device application, proceed as follows:
MULTI-DEVICE APPLICATION
In multi-dimmer installations, the reduction of the dimmer's capacity
is required. Breaking off fins is not required on this device. Refer to
the chart for maximum load per dimmer.
MAXIMUM LOAD PER DIMMER FOR MULTI-DEVICE
More than
Cat. No.
Single
Two Devices 2 Devices
ACEØ4
400W
350W
250W
ACEØ6
600W
500W
400W
INSTALLING YOUR DIMMER
NOTE: Use check boxes
when Steps are completed.
WARNING:
TO AVOID FIRE, SHOCK, OR DEATH;
Step 1
TURN OFF POWER at circuit breaker or fuse and test
that power is off before wiring!
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Single Pole (One location) or 3-Way (Multi-location)
Identifying your wiring application (most
Step 2
common):
NOTE: If the wiring in the wall box does not resemble
any of these configurations, consult a qualified electrician.
2
2
1
1
3
3
4
4
5
Single-Pole
3-Way
1. Line (Hot)
1. Line or Load (See important
instruction below)
2. Neutral
3. Ground
2. Neutral
4. Load
3. Ground
4. First Traveler – note color
5. Second Traveler – note color
NOTE: For matching remote w/LEDs
installation, the First Traveler becomes
Line Hot.
IMPORTANT: For 3-Way applications, note that one of the screw
terminals from the old switch being removed will usually be a different
color (Black) or labeled Common. Tag that wire with electrical tape
and identify as the common (Line or Load) in both the dimmer wall
box and remote wall box.
Preparing and connecting wires:
Step 3
Pull off pre-cut insulation from dimmer leads.
Make sure that the ends of the wires from the
wall box are straight (cut if necessary). Remove
insulation from each wire in the wall box as shown.
5/8"
Cut
(1.6 cm)
(if necessary)
Strip Gage
(measure bare wire here)
Electronic Low-Voltage Dimmer (Lighted)
Cat. No. ACEØ4-1L, 400W
Cat. No. ACEØ6-1L, 600W
120VAC, 60Hz
INSTALLATION INSTRUCTIONS
WARNINGS AND CAUTIONS:
• Lighting fixture and dimmer must be grounded.
• This dimmer must be installed in a wall box with a neutral connection.
• Consult fixture manufacturer to determine if their solid state transformers can be dimmed.
• Total minimum load must exceed 40W.
• Dimmer may feel warm to the touch during normal operation.
• Recommended minimum wall box depth is 2-1/2".
• Maximum wire length from dimmer to all installed remotes cannot exceed 300 ft.
• Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture.
• Use this device only with copper or copper clad wire. With aluminum wire use only devices marked CO/ALR or CU/AL.
Step 3 cont'd
For non-standard wiring applications, refer
to Wire Nut and Connector Size Chart
WIRE CONNECTOR / # OF COND.
COMBINATION CHART
1 - #12 w/ 1 to 3 #14, #16 or #18
2 - #12 w/ 1 or 2 #16 or #18
1 - #14 w/ 1 to 4 #16 or #18
2 - #14 w/ 1 to 3 #16 or #18
Installing your Alignment Plate:
Step 4
Important Notice for Installer
To achieve proper aesthetic installation of the Acenti
products, the wall surface surrounding the wall box opening
must be fairly flat and free of irregularities. The wall box
must be level and recessed or flush to the wall surface. The
Acenti installation system allows for adjustments that will
correct minor flaws that may be present in the installation
area.
This device must be installed with the Acenti™ Alignment
Plate. The Alignment Plate is packaged with the Acenti™
Wallplate, which is sold separately from this device.
The Alignment Plate will function properly only if it is
mounted to a flat wall surface as described above.
• Leviton recommends to temporarily position the Alignment
Plate prior to wiring the device. If the wall box wires
extend at least 6 inches out of the wall box, it is also
possible to install the Alignment Plate after the device has
been wired (refer to Wallplate instruction sheet).
• The Alignment Plate must be installed with the tab
towards the bottom.
• Leviton recommends the following 3 methods to
temporarily hold the Alignment Plate – use of device
mounting screw, use of wall box wires, or use of electrical
tape (refer to the following figures):
Step 4 cont'd
Alignment Plate Held By Mounting Screw
Mounting
Screw
Alignment
A
Plate
Alignment Plate Held By Wires
B
Alignment Plate Held By Tape
Electrical
Tape
C
• For Single-Pole Application, go to Step 5a.
• For 3-Way Coordinating Remote (no LEDs) Application, go to Step 5b.
• For 3-Way Matching Remote (with LEDs) Application, go to Step 5c.
Installing your Dimmer –
Step 5a
Single-Pole Wiring Application:
Black
1
White
2
Green
3
Red
4
Yellow/Red
Insulating label:
This wire is used in 3-way installations only.
For single pole installations, do not remove
this insulating label.
Dimmer
White
Black
Hot (Black)
Green
Ground
Red
Yellow/Red
Electronic
Low-Voltage
Black
Insulating
Transformer
Line
Label
120VAC, 60Hz
Primary
Side
White
Neutral (White)
WIRING DIMMER:
Connect wires per WIRING DIAGRAM as follows:
• Green or bare copper wire in wall box to Green dimmer lead.
• Line Hot wall box wire to Black dimmer lead.
• Load wall box wire to Red dimmer lead.
• Line Neutral wall box wire to White dimmer lead.
• Yellow/Red wire should have Red insulation label affixed.
NOTE: If insulating label is not affixed to Yellow/Red dimmer
lead, use electrical tape to cover.
• Proceed to Step 6.

Advertisement

loading

Summary of Contents for Leviton Acenti ACE04-1L

  • Page 1 • To avoid overheating and possible damage to this device and other equipment, do not install to control a receptacle, fluorescent lighting, a motor- or a transformer-operated appliance. • Use with electronic low-voltage transformers only. Do Not use to control a magnetic low-voltage transformer. Use a Leviton magnetic low-voltage dimmer to control magnetic low-voltage transformers.