E6580516
Table 6.2.3 Control circuit terminal functions
Control circuit terminal functions are as shown below. The internal circuit diagrams for each terminal
are shown on page 22.
Internal
Terminal
symbol
Terminal function
circuit
diagram
FLA,FLB,FLC
These are the multifunction programmable relay contact outputs(refer
E
to page 12)The contact ratings are 250Vac-2A(COS
+
= 1 ), 30Vdc-1 A,
250Vac-1A(COS ¢ =0.4).
The standard function setting detects when the inverter protection
function have operated.
When a protection function activates, FLA-FLC will close, and FLB-FLC
will open.
P24
24Vdc power output. (Max. 1 OOmA)
F
RCH
This is a multifunction programmable open-collector output(refer to
G
page 62). (Max.50mAdc)
The standard function setting activates this signal when completion of
deceleration or acceleration is detected.
LOW
This is a multifunction programmable open collector output( refer to
G
page 62). (Max. 50mAdc)
The standard function setting activates this signal when a low speed is
detected.
FP
This is a dedicated open-collector output. (Max.50mAdc). Pulses that
H
are 48-, 96- or 360-times the output frequency are output according to
parameter settings.
The standard setting is for 48-times the output frequency.
FM
This is a multifunction programmable analog output(refer to page 94. )
I
The standard setting is the pre-compensation reference frequency.
When connecting a meter, use a 1 mAdc full-scale ammeter or 7 .5Vdc-
1 mA full-scale voltmeter.
AM
This is a multifunction programmable analog output(refer to page 94. )
I
The standard setting is the output current. When connecting a meter,
use a 1 mAdc full-scale ammeter or 7.5Vdc-1 mA full-scale voltmeter.
pp
This is the power supply for reference frequency setting. (1 OVdc)
J
Connect a 3k
Q
potentiometer (a 1 to 1 Ok
Q
potentiometer may also be
used).
RR
This is a multifunction programmable analog input.
K
The standard setting is a 0 to 1 OVdc input corresponding to a O to
BOHz frequency setting.
IV
This is a multifunction programmable analog input. Change between O
L
to 1 OVdc (SW at V side) or 4 (0) to 20mAdc (SW at I side) via SW,
located under the ROM interface window. The standard setting is a O
to 1 OVdc input corresponding to a 0 to 80Hz frequency setting with the
switch at the V side.
RX
This is a multifunction programmable +/- analog input. Change
M
between 0 and 1 OVdc (SW at 1 OV side) or O to ±5Vdc (SW at 5V
side) via SW, located under the ROM interface window. The standard
setting is a 0 to ±
1
OVdc input corresponding to a Oto 80Hz
forward/reverse frequency setting with the switch at the
1
OV side.
cc
This is the control circuit common terminal.
N
- 19 -