2.22 SETTINGS

No
Temperature Set Points Page
1-
Inlet Air Temp. - Low Alarm Setpoint
2-
Inlet Air Temp. - High Alarm Setpoint
3-
Exchanger Temp. - Low Alarm Setpoint
4-
Exchanger Temp. - High Alarm Setpoint
5-
Low Pressure Line Temp. - Low Alarm Setpoint
6-
Low Pressure Line Temp. - High Alarm Setpoint
7-
High Pressure Line Temp. - Low Alarm Setpoint
8-
High Pressure Line Temp. - High Alarm Setpoint
9-
Ambient Temperature - Low Alarm Setpoint
10-
Ambient Temperature - High Alarm Setpoint
11-
Exchanger Temp. - ECO Start Setpoint
12-
Exchanger Temp. - ECO End Setpoint
13-
Condenser Temp. - Dif. Setpoint
No
Time Parameters Page
1-
Exchanger Temp. - Alarm Delay (Minute)
2-
ECO Start Delay (Minute)
3-
Low Pressure Line Temp. - High Alarm Delay (Minute)
4-
Restart Delay (Second)
5-
Drain Off Time (Minute)
6-
Drain On Time (Second)
7-
Filter Change Period (Hour)
8-
General Maintenance Period (Hour)
What does it show?
The bottom limit of the Dryer air inlet temperature
The top limit of the Dryer air inlet temperature
The bottom limit of the refrigerant gas temperature in the Evaporator
The top limit of the refrigerant gas temperature in the Evaporator
The bottom limit of the refrigerant gas temperature in the
Low pressure side of the refrigerant circuit
The top limit of the refrigerant gas temperature in the
Low pressure side of the refrigerant circuit
The bottom limit of the refrigerant gas temperature in the
High pressure side of the refrigerant circuit
The top limit of the refrigerant gas temperature in the High pressure
side of the refrigerant circuit
The bottom limit of the Ambient air temperature
(Dryer room temperature)
The top limit of the Ambient air temperature
(Dryer room temperature)
Dryer stops automatically when the evaporation
temperature goes below that temperature
Dryer starts automatically when the evaporation
temperature goes above that temperature
Temperature between refrigerant inlet and outlet of the condenser
When the dryer is turned on Controller does not read evaporator temperature for sometime
until the refrigerant circuit stabilizes
Controller does not stop the dryer during that time after the evaporation temperature goes
below the set temperature
When the dryer is turned on the controller does not measure Low and High temperatures
When the dryer stops it does not re-start for some seconds because of safety
Timer drain is "off" during that time
Timer drain is "on" during that time
Warning to the customer to replace the elements of their filters
Warning to the customer to get a service from Sullair
Set Points (°C / °F)
0 / 32
55 / 131
(-)3 / 26,6
20 / 68
(-)5 / 23
45 / 113
0 / 32
90 / 194
0 / 32
55 / 131
2 / 36
8 / 46
5 / 5
for a period of time
Ideal value that should
be seen (°C/°F)
35 / 95
2-10 / 36-50
7-20 / 45-68
40-80 / 104-176
25 / 77
Set Points
20
10
10
30
3
5
8000
20000