PHYSICAL AND ELECTRICAL DATA

MODEL
Unit Supply Voltage
1
Normal Voltage Range
Minimum Circuit Ampacity
Max. Overcurrent Device Amps
Min. Overcurrent Device Amps
Compressor Type
Rated Load
Compressor
Amps
Locked Rotor
Crankcase Heater
Factory External Discharge Muffler
Factory External Check Valve
4
HS Kit Required with TXV
Fan Diameter Inches
Rated HP
Rated Load Amps
Fan Motor
Nominal RPM
Nominal CFM
Face Area Sq. Ft.
Coil
Rows Deep
Fins / Inch
Liquid Line Set OD (Field Installed)
Vapor Line Set OD (Field Installed)
6
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
Operating Weight Lbs.
* Models with "H" on the end of the model number are shipped with a Hard Start Kit installed at the factory.
1. Rated in accordance with AHRI Standard 110-2012, utilization range "A".
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.
5. For applications with non-standard vapor line sizes, see the "Applications & Accessories" section of this Technical Guide.
6. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract
the amount of refrigerant, using the difference in actual lineset length (not the equivalent length) multiplied by the per foot value.
A
Johnson Controls Unitary Products
YCE18B21H
YCE24B21H
10.2
11.6
2
15
20
3
15
15
Recip
Recip
7.7
8.6
45.0
45.0
No
No
No
No
No
No
Yes*
Yes*
18
22
1/12
1/8
0.64
0.80
1000
1075
1900
2875
12.37
13.83
1
1
23
23
3/8
3/8
5
3/4
3/4
3 - 14
3 - 12
0.62
0.62
140
155
C
B
A0339-001
YCE30B21H
YCE36B21H
208-230V, 1 60Hz
187 to 252
14.2
18.9
20
30
15
20
Recip
Recip
10.7
14.1
57.0
78.0
No
No
No
No
No
No
Yes*
Yes*
22
22
1/8
1/4
0.80
1.30
1075
850
2950
3275
13.83
17.37
1
1
23
23
3/8
3/8
3/4
3/4
4 - 3
4 - 14
0.62
0.62
155
180

DIMENSIONS

Unit
Model
A
YCE18B21H
33-1/4
YCE24B21H
30
YCE30B21H
30
YCE36B21H
36-1/4
YCE42B21H
33-1/4
YCE48B21S
33-1/4
YCE60B21S
36-1/4
‡ Adapter fitting must be field installed for the required 1-1/8" line set.
All dimensions are in inches and are subject to change without notice.
Overall height is from bottom of base pan to top of fan guard.
Overall length and width include screw heads.
5005746-YTG-A-0815
YCE42B21H
YCE48B21S
21.5
25.7
35
45
25
30
Recip
Scroll
16.2
19.5
88.0
130.0
No
No
Yes
No
No
No
Yes*
No
24
24
1/4
1/4
1.30
1.30
850
850
3500
3500
18.74
18.74
1
1
23
23
3/8
3/8
7/8
7/8
5 - 2
4 - 15
0.67
0.67
215
200
Dimensions
Refrigerant Connection
(Inches)
Service Valve Size
B
C
Liquid
24
24
29-1/4
29-1/4
29-1/4
29-1/4
29-1/4
29-1/4
3/8
35-1/4
31-3/4
35-1/4
31-3/4
38
34-1/4
YCE60B21S
31.7
50
35
Scroll
24.3
144.2
No
No
No
No
26
1/4
1.30
850
4300
23.40
1
23
3/8
1-1/8
5 - 12
0.75
205
Vapor
3/4
7/8
7/8
3

Advertisement

Table of Contents
loading

Table of Contents