RXTQ-TAVJ9A / TAVJUA
[3] –3 Calculate the corrected capacity of the outdoor unit.
- Calculate the connection ratio of the system.
Total CI = 69, CI of RXTQ60TAVJUA = 57
Connection ratio = 69 / 57 = 121%
- Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air temperature, and connection
ratio.
* I n case the outdoor air temperature, the indoor air temperature, or the connection ratio falls between temperatures listed in the table, calculate the
capacity by interpolation.
RXTQ60TAVJUA Cooling Capacity for Standard Condition (Te: 43°F)
Connection ratio
120%
Cooling capacity
62.6
(B) = 62.6 + (63.7 – 62.6) × (121 – 120) / (130 – 120)
= 62.7
121%
130%
(B)
63.7
47
EDUS331608C-D