General Information Screen; Unit Status Screen - Daikin Maverick I Operation Manual

Package air conditioner ddc rooftop unit controller
Table of Contents

Advertisement

General Information Screen

This is the home page of the system. At power up or after a
period of time of 5 minutes (display delay) without the selection
of any buttons, the system returns to this screen and resumes
scrolling through the items of this group.
The general information screen automatically scrolls through
the different menu items at 2-second intervals. When the user
presses any button, the changing of screens stops until the
display delay expires.
The software is programmed in the factory and cannot be
changed. The item "Alarms" is dependent upon the existence
of an alarm and it may display either "No Active Alarm" or
"Check Alarms!" Another screen outside this group shows the
details of existing alarms. The option for system configuration
is set with a configuration key from the factory.
www.DaikinApplied.com

Unit Status Screen

The status screen shows basic information about the operation
of the unit, such as mode of operation, inputs, outputs, and
capacity of cooling or heating.
Table 7: Unit Status Screen
Item
Mode
Inputs
Outputs
Capacity
19
u
I
ser
nTerfaCe
Range
STANDBY
Fan Only
COOL STG1 ECON
COOL STG2 CC/ECO
COOL STG1 COMP
COOL STG2 COMP
HEAT STG1 COMP
HEAT STG2 COMP
HEAT STG1 ELEC
HEAT STG2 ELEC
HEAT STG1 GAS
HEAT STG2 GAS
HEAT STG2 CC/ELE
HEAT STG3 CC/ELE
HEAT STG4 CC/ELE
Defrost 1
Defrost 2
24VAC Inputs
Y1 – ON/OFF
Y2 – ON/OFF
W1 – ON/OFF
W2 – ON/OFF
B – ON/OFF
G – ON/OFF
OCC – ON/OFF
LPS1 – ON/OFF
LPS2 – ON/OFF
HPS1 – ON/OFF
HPS2 – ON/OFF
CFS – ON/OFF
SMKS – ON/OFF
FPS – ON/OFF
Compressor 1 – ON/OFF
Compressor 2 – ON/OFF
Rev Vlv 1 – ON/OFF
Rev Vlv 2 – ON/OFF
Heat 1 – ON/OFF
Heat 2 – ON/OFF
Outdr Fan 1 – ON/OFF
Outdr Fan 2 – ON/OFF
Indoor Fan – ON/OFF
Heating / Cooling – 100%
OM 1077-1 • MAVERICK I