4. Auto Address Setting

4. Auto Address Setting

Basic wiring diagram: Example (1)
1
2
(1) Automatic Address Setting from the Outdoor Unit
1.
On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to "1" and that the DIP
switch (S003) is set to
3
2.
To set the number of indoor units that are connected to the outdoor unit to 10, on the outdoor main unit control PCB set the
No. of indoor units DIP switch (S005) to
3.
To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (S006) to
4
ON
ON
(2 units), and set the unit No. DIP switch (S007) to
1
2
3
OFF
4.
On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to
5
5.
Turn ON the power to the indoor and outdoor units.
6.
On the outdoor main unit control PCB, short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.
(Communication for automatic address setting begins.)
6
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.
The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)
7
7.
Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller and
complete automatic address setting.
Refer to "Automatic Address Setting from the Remote Controller."
8
• If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 (main unit)
settings
No. of indoor units
(10 units setting)
System address
(S004)
(system 1 setting)
0
(S002)
(S003)
ON
ON
(S005)
ON
1
2
OFF
1
2
No. of
(S006)
Unit number
outdoor
ON
ON
ON
setting
units (2 units
(Unit No. 1)
setting)
1
2
3
OFF
Unit
Outdoor Unit
No. 1
(Main)
1-1
Indoor Unit
Remote controller
ON
ON
"0." (These are the settings at the time of factory shipment.)
1
2
OFF
ON
1
2
No. 2 (sub unit)
ON
settings
3
OFF
Unit
(S007)
(S007)
number
ON
ON
setting
1
2
3
(Unit No. 2)
1
2
3
OFF
Unit
No. 2
Outdoor main/sub
(Sub)
control wiring
Inter-unit control wiring
1-2
1-3
Remote controller
cross-over wiring
ON
"1," and set the rotary switch (S004) to "0."
3
OFF
ON
1
2
3
ON
1
5-6
ON
OFF
1-10
Fig. 5-5
(unit No. 1 – main).
(unit No. 2).
2
3
Test Run