Bryant Preferred Series Service And Maintenance Instructions page 13

Gas heat/electric cooling with puron (r-410a) refrigerant
Hide thumbs Also See for Preferred Series:
Table of Contents

Advertisement

POINT NAME
Humidistat/LTLO
Thermostat W1
Econ Y1
Thermostat G
24V Power (J1)
24V Power (J2)
Econ Y2
COMP1
IFM
COMP2
LSV
DSV1
NOT LSV
DSV2
LEGEND
COMP
— Compressor
CTB
— Control Terminal Board
DI
— Discrete Input (switch)
DO
— Discrete Output (switch)
DSV
— Discharge (gas) Solenoid Valve
Y1
Y2
W1
G
HUM/LTLO
OFF OFF
OFF
ON
ON OFF
OFF
On
ON
ON
OFF
ON
OFF OFF
ON
X
OFF OFF
OFF
ON
ON OFF
OFF
ON
ON
ON
OFF
ON
OFF OFF
ON
X
OFF OFF ON+W2
X
PROBLEM
Subcooling Reheat Mode Will Not
Activate
Hot Gas Reheat Mode Will Not
Activate
Table 2 — Perfect Humidity Reheat Control Board I/O
TYPE
CONNECTION PIN NUMBER
DI, 24VAC
DI, 24VAC
DI, 24VAC
DI, 24VAC
24VAC
24VAC
DI, 24VAC
DO, 24VAC
DO, 24VAC
DO, 24VAC
DO, 24VAC
DO, 24VAC
DO, 24VAC
DO, 24VAC
Table 3 — Inputs/Modes/Outputs Summary
MODE
OFF
Normal
OFF
Normal
OFF
Normal
OFF
Normal
ON
Reheat
Dehumidify
Cool1 and
Subcool Cir1/
ON
Cool2/Subcool-
Reheat Cir2
Dehumidify
Cool1 and
Subcool Cir1
ON
Cool2/Subcool-
and Cir2
Dehumidify
ON
Heat Override
ON
Heat Override
Heat 1 and 2
Table 4 — Perfect Humidity Troubleshooting
CAUSE
General cooling mode problem.
No dehumidification demand.
CRC relay operation.
Circuit RLV, CLV or LDV valve problem.
General cooling mode problem.
No dehumidification demand.
CRC relay operation.
Circuit RLV, CLV or LDV valve problem.
Circuit RDV valve is not open.
Outdoor temperature too low.
J1A-1 (1)
J1A-2 (2)
J1A-6 (6)
J1B-1 (7)
J1B-3 (9)
J2-1
J1B-5 (11)
J1A-5 (5)
J1B-4 (8)
J1B-4 (10)
J2-2
J2-3
J2-4
J2-5
Econ
— Economizer
FPT
— Freeze Protection Thermostat
IFM
— Indoor (Supply) Fan motor
LSV
— Liquid Solenoid Valve
LTLO
— Low Temperature Lockout
REHEAT — Connection Strip REHEAT (on CTB)
COMP1 COMP2
Fan
OFF
OFF
Cool1
ON=Y1
OFF
Cool2
ON=Y2
ON
Heat 1
OFF
OFF
ON
ON
ON
ON
ON
ON
Heat 1
OFF
OFF
OFF
OFF
See Cooling Service Troubleshooting (Table 5).
See No Dehumidification Demand, below.
See CRC Relay Operation, below.
See CLV, RLV or LDV Valve Operation, below.
See Cooling Service Troubleshooting (Table 5).
See No Dehumidification Demand, below.
See CRC Relay Operation, below.
See CLV, RLV or LDV Valve Operation, below.
See RDV Valve Operation, below.
Check Reheat2 Circuit Limit Temperatures
(ConfigurationHMZRRA.LO and RB.LO) using
ComfortLink Scrolling Marquee.
13
UNIT CONNECTION
LTLO
CTB-REHEAT-4
CTB-REHEAT-5
CTB-REHEAT-1
CTB-R
CTB-R
CTB-REHEAT-7
CTB-HEAT-6
CTB-REHEAT-2
CTB-REHEAT-8
FTP (BLK)
DSV
IFM
LSV1 LSV2 LSV NOT
ON=G
OFF
OFF
ON=R
ON=G
OFF
OFF
ON=R
ON=G
OFF
OFF
ON=R
ON=G
OFF
OFF
ON=R
ON=G
ON
ON
OFF
ON=G
ON
ON
OFF
ON=G
ON
ON
OFF
ON=G
OFF
OFF
ON=R
ON=G
OFF
OFF
ON=R
REMEDY
NOTE
2-circ only
2-circ only
2-circ only
DSV1
DSV2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON=R ON=R
OFF
ON=R
OFF
OFF
OFF
OFF
OFF
OFF