ALTERATIONS REQ'D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE
COOLING UNIT
24,000
30,000
36,000
42,000
48,000
Speed Tap \
Static
Pressure
0.1
Low
743
ML
931
MH
1309
High
1561
Speed Tap \
Static
Pressure
0.1
Low
74
ML
59
MH
42
High
35
Furnace Motor Current Draw (Amps) vs. External Static pressure (in.
Speed Tap \
Static
0.1
Pressure
Low
3.04
ML
3.85
MH
5.40
High
6.60
Speed Tap \
Static
Pressure
0.1
Low
301
ML
387
MH
582
High
735
HTG
Speed
MED LOW
MED LOW
MED LOW
MED LOW
MED LOW
Furnace Airflow (CFM) vs. External Static pressure (in. WC.)
0.2
0.3
712
698
923
891
1267
1241
1504
1458
Temperature Rise vs. External Static Pressure (in. WC.)
0.2
0.3
78
79
60
62
43
44
36
38
0.2
0.3
2.93
2.88
3.78
3.66
5.23
5.06
6.41
6.22
Furnace Motor Watts vs. External Static pressure (in. WC.)
0.2
0.3
298
294
391
381
565
551
717
702
=
Recommended operation range
GMC1-75
Recommended CLG
Speed
LOW
MEDIUM LOW
MEDIUM HIGH
MEDIUM HIGH
HIGH
0.4
0.5
656
612
863
847
1198
1141
1392
1327
0.4
0.5
84
90
64
65
46
48
39
41
WC.)
0.4
0.5
2.79
2.72
3.55
3.45
4.88
4.70
6.04
5.85
0.4
0.5
290
282
374
369
535
516
678
661
25
0.6
0.7
562
515
789
727
1099
1036
1261
1182
0.6
0.7
98
107
70
76
50
53
44
47
0.6
0.7
2.64
2.53
3.31
3.15
4.52
4.30
5.65
5.43
0.6
0.7
277
269
353
345
505
481
639
617