HISTORY Key Operation
The HISTORY key provides the user access to many
unit and system operating parameters captured at the
instant a unit or system safety (fault) shutdown occurs.
The history buffer will also capture system data at the
time of normal shutdowns such as cycling shutdowns.
When the HISTORY key is pressed the following screen
is displayed:
HISTORY
CHOOSE HISTORY TYPE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
The ◄ and ► (ARROW) keys allow choosing between
NORMAL SHUTDOWNS and FAULT SHUTDOWNS.
"Fault" shutdowns provide information on safety
shutdowns, while "Normal" shutdowns provide chiller
cycling information on temperature (demand), cycling,
remote, system switch, etc., shutdowns that are non-safe-
ty related shutdowns. Once the selection is made, the
√ (ENTER) key must be pressed to enter the selection.
JOHNSON CONTROLS
JOHNSON CONTROLS

HISTORY KEY

Normal Shutdowns History
If the NORMAL SHUTDOWNS History is selected,
the following screen will be displayed:
NORM HIST XX 18-JUN-20004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
XX is the normal shutdown number. The display will
provide date and time of the shutdown and the reason
for the cycling shutdown (YYY....).
The operator can view any of the stored 20 single display
normal shutdown history buffers. History buffer number
1 provides the most recent shutdown information and
buffer number 20 is the oldest safety shutdown informa-
tion saved. The ◄ and ► (ARROW) keys allow scrolling
between each of the history buffers. The ► (ARROW)
key scrolls to the next normal history shutdown and the
◄ (ARROW) key scrolls to the previous normal history
shutdown.
The following display will typically be displayed on a
normal shutdown due to shutdown on lack of cooling
demand.
NORM HIST XX 18-JUN-20004 10:34:58 AM
SYS X COOLING DEMAND SHUTDOWN
FORM 201.21-NM4 (1020)