Powering The System; Table 9. Pcs-822 Field Shelf Power Consumption And Heat Dissipation - ADC PG-Flex Plus Technical Practice

Field shelf
Hide thumbs Also See for PG-Flex Plus:
Table of Contents

Advertisement

SCP-PCS822-021-03H

Powering the System

Table 9
summarizes the powering requirements and heat dissipation for the PSC-822 when it is fully populated with
a battery voltage of –48.0 V, and with all CO to RT distances at their maximum DSL reach. The table provides the
average current drawn for a fully populated Field Shelf under these conditions.
The conditions in
Each configuration assumes the use of one Management Unit and 2 MUXs

Table 9. PCS-822 Field Shelf Power Consumption and Heat Dissipation

Service
4 POTS
(dual)
6 POTS
(dual)
3 POTS, 1 ISDN
(dual)
2 ISDN
(dual)
6 UVG
(dual)
24 POTS
c
(No Doublers)
24 POTS
c
(1 Doubler)
24 POTS
c
(2 Doublers)
24 POTS
d
(No Doublers)
24 POTS
d
(1 Doubler)
24 POTS
d
(2 Doublers)
3 POTS/1 ADSL
6 POTS/1 ADSL
8 ADSL (Dual)
a. Indicates the current when all lines are off hook with all DSL lines at maximum length with -48 Vdc battery
b. Indicates the recommended fuse for -42.5 Vdc battery and 15% fuse margin
c. Indicates the subscriber drop set for LONG is ≤ 960 Ω
d. Indicates the subscriber drop set for SHORT is ≤ 830 Ω
Please refer to the appropriate AMX/PMX and AMU/PMU Technical Practice for system configuration
options.
30
Table 9
assume that the POTS lines at all customer sites are off hook.
Models
PLL-735
PRL-770
PLL-735
PRL-771
PLL-735
PRL-772
PLL-735
PRL-773
PLL-735
PRL-779
FLL-814
FRL-842
FLL-814
FRL-842
FLL-814
FRL-842
FLL-814
FRL-842
FLL-814
FRL-842
FLL-814
FRL-842
ALU-935
ARB-963
ALU-935
ARB-964
ALU-935
ARL-942
Input Current
a
Fuse
4.9 A
7.5 A
6.0 A
10.0 A
4.7 A
7.5 A
3.8 A
7.5 A
5.1 A
7.5 A
5.7 A
10.0 A
7.1 A
10.0 A
8.4 A
12.0 A
4.9 A
7.5 A
5.7 A
10.0 A
6.6 A
10.0 A
5.6 A
7.5 A
6.1 A
10.0 A
7.1 A
10.0 A
January 6, 2003
(Table
9).
b
Heat Dissipation
82.6 W
90.1 W
84.0 W
81.6 W
99.0 W
82.2 W
92.0 W
101.2 W
76.7 W
82.8 W
88.6 W
99.4 W
93.0 W
101.3 W
ADC Telecommunications, Inc.