Part Description
6) Remove knock out shapes on the rear case (2-sided) according to the connector's size and direc-
tion.
7) Connect the connection wires properly according to the connection. When connecting CN-POWER
and CN_DRY(L) to the power cable in the terminal block, make sure to put them inside the square
hole of the Clamp as shown in the picture.
8) Set the switch according to the setting method. (Refer to the instruction)
9) Combine top part of the metal case with the back side of the metal case.
10) Hang the front of the case to the rear case hook and tighten the fixing screws on the bottom part.
1. Install the product on flat surface and install anchoring screws at more than 2 places. Otherwise
the central controller may not be anchored properly.
2. Do not tighten anchoring screws too tightly. It may cause deformation of the case.
3. Do not deform the case at random. It may cause malfunction of the central controller.
12 Dry Contact

Installation Guide

Step 1
Connect CN-CC with Indoor PCB by the cable(provided)
- Connection of Dry contact only
DRY CONTACT
Indoor unit
CN-CC
CN-CC
PCB
CN-CC
- Connection of Dry contact & LG Central Controller in case of single constant models.
Indoor unit
PCB
CN-CC
CN-CC
CN-CC
CN-CC
PI485 : Connect to central controller
* Single Only
- When you install single product this PCB have to add.
Installation Guide
CN-CC
AC 220V
DRY CONTACT
AC 220V
Installation Manual 13