Maintenance

Maintenance Procedures

Weekly/Monthly Maintenance

While unit is running in stable conditions, inspect the entire
system for unusual conditions and inspect the condenser
coils for dirt and debris. If the coils are dirty, refer to coil
cleaning in RTAC-SVX01*-EN.
Call Trane Rental Services Technical Support for any
unusual conditions or repairs needed.

Decommissioning Procedure

1. Press STOP key on the CH530 DynaView control.
Allow enough time for compressors to go through the
unload sequence and shut down.
2. Turn the chilled water pump to the OFF position.
3.
Turn evaporator heater switch, located on the shore
power/cam connection panel, to OFF position.
Note: Local codes and regulations apply for disposal of
glycol or anti-freeze solutions.
4. Drain solution from system. If the system has glycol or
other anti-freeze solution, flush hoses and evaporator
with water. Refer to Trane Rental Services Freeze
Protection Procedure if decommissioning is taking
place during a time that could see below freezing
ambient temperatures.
40
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious
injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with a CAT III or IV
voltmeter rated per NFPA 70E that all capacitors have
discharged.
5. Disconnect power supply.
6. Secure any loose panels. Replace any sheet metal
screws or bolts to prevent panel from blowing off during
transportation.
7. Return hose, fittings or cables (if furnished by Trane
Rental Services) to appropriate containers for return
shipment.
8. If applicable, return leveling jacks on F2-F4 style
machines to shipping position.
9. Notify Trane Rental Services if unit needs repairs or
has damage.