The maximum power consumption and heat dissipation depends upon the type of remote and regenerator units in
the system and the CPE power setting.
The three most important power parameters of an H2TU-C are its maximum power consumption, its maximum
power dissipation and its maximum current drain.
Table 24
describes line-powered circuits on 9 kft, 26 AWG loops without a regenerator.
H2TU-R Model No.
H2TU-R-402
M
P
AXIMUM
OWER
The maximum power dissipation measures the power that is converted into heat that builds up within the unit. It
contributes to the total heat generated in the space around the unit. It is used to determine the maximum number
of fully loaded shelves per bay that does not exceed the maximum allowable power dissipation density in
watts per square foot to comply with GR-63.
In COs, the maximum power dissipation for open-faced, natural convection-cooled mountings is limited to
134.7 watts per square foot per GR-63-CORE. The footprint of a standard 28-slot, 23-inch HCS-417 shelf is
7.024 square feet. Therefore, the maximum bay dissipation is limited to 946 watts. Use this limit and the
parameters in
Table 24
This is a worst case situation since it assumes the entire CO is subjected to the maximum power
density. More favorable conditions would permit increasing the number of shelves per bay
without jeopardizing the CO thermal integrity.
The thermal loading limitations imposed when using the H2TU-C in a Controlled Environmental Vault (CEV) or
other enclosures are determined by applying its power parameters to the manufacturer's requirements for each
specific housing.
The -42.5 Vdc power consumption is the maximum total power that the H2TU-C consumes or draws from the
shelf power source. This parameter is needed when the H2TU-C is in a location remote to the CO it is serving. It
determines the battery capacity required to maintain an 8-hour, stand-by battery reserve for emergency situations.
Battery capacity, therefore, limits the maximum number of line units which can be installed in a remote enclosure.
Use the data in
Table 24
M
C
AXIMUM
URRENT
The maximum current drain is the maximum current drawn from the shelf power supply when its at its minimum
voltage (-42.5
). This determines the shelf fusing requirements. Use the -42.5 Vdc current data in
Vdc
determine the shelf fusing requirements for your particular H2TU-C applications.
52
Table 24. H2TU-C Power Parameters—No Regenerator
H2TU-R
-42.5 Vdc Power
CPE Power
Consumption (Watts)
Typical
11.5
D
ISSIPATION
to determine the maximum number of H2TU-C circuits that can occupy one CO bay.
to perform this analysis.
D
RAIN
April 21, 2000
Heat Dissipation (Watts)
Maximum
Typical
12.5
6.0
152-202-115-04, Revision 04
-42.5 Vdc Current (mA)
Maximum
Typical
7.0
270
H2TU-C-202 List 1E
Maximum
294
Table 24