ABB 620 Series Manual

ABB 620 Series Manual

Motor protection and contro
Hide thumbs Also See for 620 Series:
Table of Contents

Advertisement

Quick Links

®
Relion
620 series
Motor Protection and Control
REM620
IEC 60870-5-103 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB 620 Series

  • Page 1 ® Relion 620 series Motor Protection and Control REM620 IEC 60870-5-103 Point List Manual...
  • Page 3 Document ID: 1MRS757657 Issued: 2013-05-07 Revision: A Product version: 2.0 © Copyright 2013 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............7 This manual..................7 Intended audience................7 Product documentation...............7 Product documentation set............7 Document revision history.............8 Related documentation..............8 Symbols and conventions..............8 Symbols..................8 Document conventions..............9 Functions, codes and symbols............10 Section 2 IEC 60870-5-103 data mappings........15 Overview...................15 Supported functions................15 Indications and controls..............18 General Data(FUN=0) IEC 60870-5-103 standard......18...
  • Page 8 Table of contents LD0.MAPGAPC2 Multipurpose analog protection function (2)....................27 LD0.MAPGAPC3 Multipurpose analog protection function (3)....................27 LD0.MAPGAPC4 Multipurpose analog protection function (4)....................28 LD0.MAPGAPC5 Multipurpose analog protection function (5)....................28 LD0.MAPGAPC6 Multipurpose analog protection function (6)....................28 LD0.MAPGAPC7 Multipurpose analog protection function (7)....................28 LD0.MAPGAPC8 Multipurpose analog protection function (8)....................29 LD0.MAPGAPC9 Multipurpose analog protection function (9)....................29...
  • Page 9 Table of contents LD0.ROVPTOV3 Residual overvoltage protection - stage 3..35 LD0.XBGGIO105 Physical binary I/O signal (status only)...35 LD0.XHBGGIO105 Physical binary I/O signal (status only)..36 LD0.XGGIO100 Physical binary I/O signals (status only)...36 LD0.XAGGIO130 Physical binary I/O signals (status only)..36 LD0.XBGGIO115 Physical binary I/O signals (status only)..37 LD0.MDSOPT1 Generic operation time supervision....37 LD0.MDSOPT2 Generic operation time supervision....37 LD0.MNSPTOC1 Negative-sequence overcurrent...
  • Page 10 1:1 LED state)................49 LD0.FKEYGGIO1 LHMI LED indications........50 LD0.SECRSYN1 Synchrocheck indications .......50 Class 2 data measurands..............51 Class 2 private measurand data (6 and 7)........52 Section 3 Interoperability profile for 620 series IEC 60870-5-103..............55 Physical layer...................55 Electrical interface...............55 Optical interface................55 Transmission speed..............55 Link layer..................55...
  • Page 11 Table of contents Earth fault indications in monitor direction......57 Fault indications in monitor direction........57 Auto-reclosure indications in monitor direction.......58 Measurands in monitor direction..........59 Generic functions in monitor direction........59 Selection of standard information numbers in control direction..................59 System functions in control direction........59 Generic functions in monitor direction........59 Basic application functions............60 Miscellaneous................60...
  • Page 13: Section 1 Introduction

    Section 1 1MRS757657 A Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 14: Document Revision History

    1.3.2 Document revision history Document revision/date Product version History A/2013-05-07 First release Download the latest documents from the ABB Website http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-103 Communication Protocol Manual 1MRS757647 Symbols and conventions 1.4.1...
  • Page 15: Document Conventions

    Section 1 1MRS757657 A Introduction of a hazard which could result in corruption of software or damage to equipment or property. The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function.
  • Page 16: Functions, Codes And Symbols

    Section 1 1MRS757657 A Introduction 1.4.3 Functions, codes and symbols Table 1: REM620 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, PHLPTOC1 3I> (1) 51P-1 (1) instance 1 Three-phase non-directional overcurrent protection, instantaneous PHIPTOC1 3I>>>...
  • Page 17 Section 1 1MRS757657 A Introduction Function IEC 61850 IEC 60617 IEC-ANSI Negative-sequence overvoltage NSPTOV1 U2> (1) 47O- (1) protection, instance 1 Negative-sequence overvoltage NSPTOV2 U2> (2) 47O- (2) protection, instance 2 Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81 (1) Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2)
  • Page 18 Section 1 1MRS757657 A Introduction Function IEC 61850 IEC 60617 IEC-ANSI Multipurpose analog protection, MAPGAPC7 MAP (7) MAP (7) instance 7 Multipurpose analog protection, MAPGAPC8 MAP (8) MAP (8) instance 8 Multipurpose analog protection, MAPGAPC9 MAP (9) MAP (9) instance 9 Multipurpose analog protection, MAPGAPC10 MAP (10)
  • Page 19 Section 1 1MRS757657 A Introduction Function IEC 61850 IEC 60617 IEC-ANSI Runtime counter for machines and MDSOPT1 OPTS (1) OPTM (1) devices, instance 1 Runtime counter for machines and MDSOPT2 OPTS (2) OPTM (2) devices, instance 2 Measurement Three-phase current measurement, CMMXU1 3I (1) 3I (1)
  • Page 20 Section 1 1MRS757657 A Introduction Function IEC 61850 IEC 60617 IEC-ANSI Time delay on (8 pcs), instance 4 TONGAPC4 TON (4) TON (4) Set reset (8 pcs), instance 1 SRGAPC1 SR (1) SR (1) Set reset (8 pcs), instance 2 SRGAPC2 SR (2) SR (2)
  • Page 21: Section 2 Iec 60870-5-103 Data Mappings

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings Section 2 IEC 60870-5-103 data mappings Overview This document describes the IEC 60870-5-103 data points and structures available in the IED. The point lists describe a superset of all data available through the standard configuration/s.
  • Page 22 Section 2 1MRS757657 A IEC 60870-5-103 data mappings Function block ME201 NSPTOV2 ● FRPFRQ1 ● FRPFRQ2 ● FRPFRQ3 ● FRPFRQ4 ● FRPFRQ5 ● FRPFRQ6 ● MNSPTOC1 ● MNSPTOC2 ● LOFLPTUC1 ● LOFLPTUC2 ● JAMPTOC1 ● STTPMSU1 ● PREVPTOC1 ● MPTTR1 ●...
  • Page 23 Section 2 1MRS757657 A IEC 60870-5-103 data mappings Function block ME201 ESXSWI1 ● DCXSWI3 ● DCXSWI4 ● ESXSWI2 ● DCSXSWI1 ● DCSXSWI2 ● ESSXSWI1 ● DCSXSWI3 ● DCSXSWI4 ● ESSXSWI2 ● ESMGAPC1 ● SECRSYN1 ● SSCBR1 ● SSCBR2 ● TCSSCBR1 ●...
  • Page 24: Indications And Controls

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings Indications and controls Table 3: Explanations of the indications and controls table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
  • Page 25: General Data(Fun=10) - 620-Specific

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.2 General Data(FUN=10) - 620-specific Table 5: General Data(FUN=10) - 620-specific IEC 61850 name SA name Description DPI value ASDU LD0.TRPPTRC1 .Op.general Trip1 input 10=On .Tr.general Trip1 output 10=On LD0.TRPPTRC2 .Op.general Trip2 input 10=On .Tr.general Trip2 output...
  • Page 26: Ld0.Mvgapc2 Multipurpose Binary Inputs (2)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .Q4.stVal Input 4 signal 10=On .Q5.stVal Input 5 signal 10=On .Q6.stVal Input 6 signal 10=On .Q7.stVal Input 7 signal 10=On .Q8.stVal Input 8 signal 10=On 2.3.4 LD0.MVGAPC2 Multipurpose binary inputs (2)
  • Page 27: Ld0.Mvgapc4 Multipurpose Binary Inputs (4)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.6 LD0.MVGAPC4 Multipurpose binary inputs (4) Table 9: LD0.MVGAPC4 Multipurpose binary inputs (4) IEC 61850 name SA name Description DPI value ASDU LD0.MVGAPC4 .Q1.stVal Input 1 signal 10=On .Q2.stVal Input 2 signal 10=On .Q3.stVal Input 3 signal...
  • Page 28: Ld0.Spcggio1 Multipurpose Binary Outputs (1)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .Rs6.ctlVal Reset flip-flop 6 10=Reset .Rs7.ctlVal Reset flip-flop 7 10=Reset .Rs8.ctlVal Reset flip-flop 8 10=Reset 2.3.9 LD0.SPCGGIO1 Multipurpose binary outputs (1) The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse- type outputs are triggered with the write value "ON".
  • Page 29: Ld0.Spcggio3 Multipurpose Binary Outputs (3)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings Table 13: LD0.SPCGGIO2 Multipurpose binary outputs (2) IEC 61850 name SA name Description DPI value ASDU LD0.SPCGGIO2 .SPCS01.ctlVal Output control 1 10/01=On/Off 1,20 .SPCS02.ctlVal Output control 2 10/01=On/Off 1,20 .SPCS03.ctlVal Output control 3 10/01=On/Off 1,20 .SPCS04.ctlVal...
  • Page 30: Ld0.Spcrggio1 Multipurpose Remote Binary Outputs (1)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCS12.ctlVal Output control 12 10/01=On/Off 1,20 .SPCS13.ctlVal Output control 13 10/01=On/Off 1,20 .SPCS14.ctlVal Output control 14 10/01=On/Off 1,20 .SPCS15.ctlVal Output control 15 10/01=On/Off 1,20 .SPCS16.ctlVal Output control 16...
  • Page 31: Ctrl.ccrdif1 Current Circuit Failure Protection

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.14 CTRL.CCRDIF1 Current circuit failure protection Table 17: CTRL.CCRDIF1 Current circuit failure protection IEC 61850 name SA name Description DPI value ASDU CTRL.CCRDIF1 .Alm.stVal ALARM Fail Alarm 10=Alarm .Op.general FAIL Fail Operate 10=Operate 2.3.15 LD0.FRPFRQ1 Frequency protection (1)
  • Page 32: Ld0.Frpfrq3 Frequency Protection (3)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.17 LD0.FRPFRQ3 Frequency protection (3) Table 20: LD0.FRPFRQ3 Frequency protection (3) IEC 61850 name SA name Description DPI value ASDU LD0.FRPTRC3 .Str.general START Stage start 10=Start LD0.FRPTOF3 Overfrequency .Op.general OPR_OFRQ -Operate 10=Operate LD0.FRPTUF3 Underfrequency .Op.general...
  • Page 33: Ld0.Frpfrq6 Frequency Protection (6)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.20 LD0.FRPFRQ6 Frequency protection (6) Table 23: LD0.FRPFRQ6 Frequency protection (6) IEC 61850 name SA name Description DPI value ASDU LD0.FRPTRC6 .Str.general START Stage start 10=Start LD0.FRPTOF6 Overfrequency .Op.general OPR_OFRQ -Operate 10=Operate LD0.FRPTUF6 Underfrequency .Op.general...
  • Page 34: Ld0.Mapgapc4 Multipurpose Analog Protection Function (4)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.24 LD0.MAPGAPC4 Multipurpose analog protection function Table 27: LD0.MAPGAPC4 Multipurpose analog protection function (4) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC4 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.25 LD0.MAPGAPC5 Multipurpose analog protection function...
  • Page 35: Ld0.Mapgapc8 Multipurpose Analog Protection Function (8)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.28 LD0.MAPGAPC8 Multipurpose analog protection function Table 31: LD0.MAPGAPC8 Multipurpose analog protection function (8) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC8 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.29 LD0.MAPGAPC9 Multipurpose analog protection function...
  • Page 36: Ld0.Mapgapc12 Multipurpose Analog Protection Function (12)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.32 LD0.MAPGAPC12 Multipurpose analog protection function (12) Table 35: LD0.MAPGAPC12 Multipurpose analog protection function (12) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC12 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.33...
  • Page 37: Ld0.Psptuv2 Positive-Sequence Undervoltage Protection - Stage 2

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.36 LD0.PSPTUV2 Positive-sequence undervoltage protection - stage 2 Table 39: LD0.PSPTUV2 Positive-sequence undervoltage protection - stage 2 IEC 61850 name SA name Description DPI value ASDU LD0.PSPTUV2 Stage 2 .Str.phsA - phsA start 10=Start .Str.phsB - phsB start...
  • Page 38: Ld0.Dphlpdoc1 Three-Phase Directional Overcurrent Protection - Low Stage (1)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.39 LD0.DPHLPDOC1 Three-phase directional overcurrent protection - low stage (1) Table 42: LD0.DPHLPDOC1 Three-phase directional overcurrent protection - low stage (1) IEC 61850 name SA name Description DPI value ASDU LD0.DPHLPTOC1 Low (1) stage .Str.phsA -phsA start 10=Start...
  • Page 39: Ld0.Phptov1 Phase Overvoltage Protection - Stage 1

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.42 LD0.PHPTOV1 Phase overvoltage protection - stage 1 Table 45: LD0.PHPTOV1 Phase overvoltage protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHPTOV1 Stage 1 .Str.phsA -phsA start 10=Start .Str.phsB -phsB start...
  • Page 40: Ld0.Phptuv1 Phase Undervoltage Protection - Stage 1

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.45 LD0.PHPTUV1 Phase undervoltage protection - stage 1 Table 48: LD0.PHPTUV1 Phase undervoltage protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHPTUV1 Stage 1 .Str.phsA -phsA start 10=Start .Str.phsB -phsB start...
  • Page 41: Ld0.Rovptov2 Residual Overvoltage Protection - Stage 2

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.49 LD0.ROVPTOV2 Residual overvoltage protection - stage 2 Table 52: LD0.ROVPTOV2 Residual overvoltage protection - stage 2 IEC 61850 name SA name Description DPI value ASDU LD0.ROVPTOV2 .Op.general OPERATE Stage 2 operate 10=Operate .Str.general START...
  • Page 42: Ld0.Xhbggio105 Physical Binary I/O Signal (Status Only)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.52 LD0.XHBGGIO105 Physical binary I/O signal (status only) Table 55: LD0.XHBGGIO105 Physical binary I/O signal (status only) IEC 61850 name SA name Description DPI value ASDU LD0.XHBGGIO105 .Ind1.stVal XHB105-Input 1 10/01=On/Off .Ind2.stVal XHB105-Input 2 10/01=On/Off .Ind3.stVal...
  • Page 43: Ld0.Xbggio115 Physical Binary I/O Signals (Status Only)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.55 LD0.XBGGIO115 Physical binary I/O signals (status only) Table 58: LD0.XBGGIO115 Physical binary I/O signals (status only) IEC 61850 name SA name Description DPI value ASDU LD0.XBGGIO115 .Ind1.stVal XB115-Input 1 10/01=On/Off .Ind2.stVal XB115-Input 2 10/01=On/Off .Ind3.stVal...
  • Page 44: Ld0.Mnsptoc1 Negative-Sequence Overcurrent Protection For Motors (1)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.58 LD0.MNSPTOC1 Negative-sequence overcurrent protection for motors (1) Table 61: LD0.MNSPTOC1 Negative-sequence overcurrent protection for motors (1) IEC 61850 name SA name Description DPI value ASDU LD0.MNSPTOC1 .Str.general START Stage1 start 10=Start .Op.general OPERATE Stage1 operate...
  • Page 45: Ld0.Mpdif1 Motor Differential Protection (1)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.63 LD0.MPDIF1 Motor differential protection (1) Table 66: LD0.MPDIF1 Motor differential protection (1) IEC 61850 name SA name Description DPI value ASDU LD0.MPDIF1 .Op.general OPERATE Stage Operate 10=Operate 2.3.64 LD0.MPTTR1 Motor thermal overload protection Table 67: LD0.MPTTR1 Motor thermal overload protection IEC 61850 name...
  • Page 46: Ld0.Arcsarc1 Fault Arc Protection - Stage 1

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.68 LD0.ARCSARC1 Fault arc protection - stage 1 Table 71: LD0.ARCSARC1 Fault arc protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.ARCSARC11 .FADet.stVal ARC_FLT_DE T Arc detected 10=Detect LD0.ARCPTRC11 .Op.general...
  • Page 47: Ld0.Efhptoc1 Non-Directional Earth-Fault And Sensitive Earth-Fault Protection - High Stage 1

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.72 LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault protection - high stage 1 Table 75: LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault protection - high stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.EFHPTOC1 High stage...
  • Page 48: Ld0.Defhpdef1 Directional Earth-Fault Protection - High Stage 1

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.76 LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1 Table 79: LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.DEFHPTOC1 High (1) stage .Str.general START -start...
  • Page 49: Ld0.Vmmxu1 Phase Voltage (1) Limit Supervision

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.80 LD0.VMMXU1 Phase voltage (1) limit supervision Table 83: LD0.VMMXU1 Phase voltage (1) limit supervision IEC 61850 name SA name Description DPI value ASDU LD0.VMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 10=Alarm .HiWrn.stVal HIGH_WARN High warning 10=Warning .LoWrn.stVal...
  • Page 50: Ctrl.cxxxxx2 Circuit Breaker (2) Cb Object And Failure Protection

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .BlkCls.stVal BLK_CLOSE Close blocked 10=Blocked CTRL.CCBRBRF1 .Str.general CB_FAULT_AL Start, timer running 10=Start .OpEx.general TRBU Failure, ext trip 10=Failure .OpIn.general TRRET Operate, retrip 10=Operate CTRL.CBCSWI1 .stSeld.stVal SELECTED...
  • Page 51: Ld0.Sscbr2 Circuit Breaker (2) Condition Monitoring

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 10=Alarm .SprChaAlm.stVal SPR_CHR_ALM Spring charge time alarm 10=Alarm .OpNumAlm.stVal OPR_ALM CB operations alarm 10=Alarm .OpNumLO.stVal OPR_LO CB operations lockout 10=Lockout .LonTmAlm.stVal MON_ALM...
  • Page 52: Ctrl.dcxswi2 Disconnector (2) - Controllable Object

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .ItlByPss.stVal ITL_BYPASS Interlocking bypass 10=Bypassed CTRL.DCXSWI1 .BlkOpn.stVal BLK_OPEN Open blocked 10=Blocked .BlkCls.stVal BLK_CLOSE Close blocked 10=Blocked CTRL.DCCSWI1 .stSeld.stVal SELECTED DC selected 10=Selected .Pos.stVal/ctlVal POSITION DC pos/control 10/01=Close/Open...
  • Page 53: Ctrl.dcxswi4 Disconnector (4) - Controllable Object

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.90 CTRL.DCXSWI4 Disconnector (4) - controllable object Table 93: CTRL.DCXSWI4 Disconnector (4) - controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.DCCILO4 .EnaOpn.stVal ENA_OPEN Open enabled 10=Enabled .EnaCls.stVal ENA_CLOSE Close enabled 10=Enabled .ItlByPss.stVal...
  • Page 54: Ctrl.dcsxswi1 Disconnector (1) - Non-Controllable Object

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .BlkCls.stVal BLK_CLOSE Close blocked 10=Blocked CTRL.ESCSWI2 .stSeld.stVal SELECTED ES selected 10=Selected .Pos.stVal/ctlVal POSITION ES pos/control 10/01=Close/Open 1,20 2.3.93 CTRL.DCSXSWI1 Disconnector (1) - non-controllable object Table 96: CTRL.DCSXSWI1 Disconnector (1) - non-controllable object IEC 61850 name...
  • Page 55: Ctrl.essxswi2 Earth Switch (2) - Non-Controllable Object

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.3.98 CTRL.ESSXSWI2 Earth switch (2) - non-controllable object Table 101: CTRL.ESSXSWI2 Earth switch (2) - non-controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.ESSXSWI2 .Pos.stVal POSITION Earth switch pos 10/01=Close/Open 2.3.99 LD0.LEDGGIO1 LHMI LED indications Type 1 (2 states)
  • Page 56: Ld0.Fkeyggio1 Lhmi Led Indications

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU 00/01/11=LED .ISCSO7.stVal LED 7 state State 00/01/11=LED .ISCSO8.stVal LED 8 state State 00/01/11=LED .ISCSO9.stVal LED 9 state State 00/01/11=LED .ISCSO10.stVal LED 10 state State 00/01/11=LED .ISCSO11.stVal...
  • Page 57: Class 2 Data Measurands

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings Class 2 data measurands Class 2 data measurands use ASDU type 9, function type 10 and information number 236 for frame 6 and 237 for frame 7. Start Length Length Start Cntrl Addr Link user data Csum...
  • Page 58: Class 2 Private Measurand Data (6 And 7)

    Section 2 1MRS757657 A IEC 60870-5-103 data mappings 2.4.1 Class 2 private measurand data (6 and 7) Class2 frames 6 and 7 are identical in this IED. Table 107: Class 2 private measurand data (6 and 7) IEC 61850 name Description Scale LD0.CMMXU1 Phase currents (1)
  • Page 59 Section 2 1MRS757657 A IEC 60870-5-103 data mappings IEC 61850 name Description Scale LD0.VSMSQI1 Sequence of voltages (1) LD0.VSMSQI1 Sequence of voltages .SeqA.c1.cVal.mag -positive magnitude .SeqA.c2.cVal.mag -negative magnitude .SeqA.c3.cVal.mag -zero magitude LD0.PEMMXU1 Power measurands (1) LD0.PEMMXU1 .TotW.instMag Active power P value 1000 .TotVAr.instMag Reactive power Q value...
  • Page 61: Section 3 Interoperability Profile For 620 Series Iec 60870-5-103

    Section 3 1MRS757657 A Interoperability profile for 620 series IEC 60870-5-103 Section 3 Interoperability profile for 620 series IEC 60870-5-103 Physical layer 3.1.1 Electrical interface ⊠ EIA RS-485 ⃞ Number of loads ......for one protection equipment NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line.
  • Page 62: Application Layer

    Section 3 1MRS757657 A Interoperability profile for 620 series IEC 60870-5-103 Application layer 3.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 3.3.2 COMMON ADDRESS of ASDU ⊠...
  • Page 63: Supervision Indications In Monitor Direction

    Section 3 1MRS757657 A Interoperability profile for 620 series IEC 60870-5-103 ⃞ <27> Auxiliary input 1 ⃞ <28> Auxiliary input 2 ⃞ <29> Auxiliary input 3 ⃞ <30> Auxiliary input 4 Note <27>...<30>: Depending on Binary I/O options and application usage there may be additional auxiliary inputs available in the IED.
  • Page 64: Auto-Reclosure Indications In Monitor Direction

    Section 3 1MRS757657 A Interoperability profile for 620 series IEC 60870-5-103 ⃞ <66> Start /pick-up L ⃞ <67> Start /pick-up N ⊠ <68> General trip ⃞ <69> Trip L ⃞ <70> Trip L ⃞ <71> Trip L ⃞ <72> Trip I>> (back-up operation) ⃞...
  • Page 65: Measurands In Monitor Direction

    Section 3 1MRS757657 A Interoperability profile for 620 series IEC 60870-5-103 3.3.3.7 Measurands in monitor direction Semantics ⊠ <144> Measurand I ⊠ <145> Measurands I, V ⊠ <146> Measurands I, V, P, Q ⊠ <147> Measurands I ⊠ <148> Measurands I...
  • Page 66: Basic Application Functions

    Section 3 1MRS757657 A Interoperability profile for 620 series IEC 60870-5-103 3.3.5 Basic application functions ⊠ Test mode ⃞ Blocking of monitor direction ⊠ Disturbance data ⃞ Generic services ⊠ Private data 3.3.6 Miscellaneous Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default MVAL scalings in this IED series is 2.4.
  • Page 67: Section 4 Glossary

    Section 4 1MRS757657 A Glossary Section 4 Glossary Autoreclosing ASDU Application-layer service data unit Double-point information Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 60870-5-103 1. Communication standard for protective equipment 2. A serial master/slave protocol for point-to-point communication IEC 61850 International standard for substation communication and modeling Intelligent electronic device...
  • Page 72 Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...

This manual is also suitable for:

Rem620