Heat Delay; Ignition Control Flash Codes; Vav Control Board Flash Codes - York ZS Series Installation Manual

Table of Contents

Advertisement

518676-BIM-C-0610
Table 30: Heat Delay
Heat
Heat
Red
Fan On
Fan Off
LED 8
Delay
Delay
60
180
On
60
90
On
60
60
On
60
30
On
45
180
On
45
90
On
45
60
On
45
30
On
30
180
Off
30
90
Off
30
60
Off
30
30
Off
0
60
Off
0
30
Off
0
10
Off
Non-std
Non-std
Off
Table 31: Ignition Control Flash Codes
Flashes
Fault Conditions
STEADY ON
Control Failure
HEARTBEAT
Normal Operation
1
Not Applicable
Pressure Switch
2
Stuck Closed
Pressure Switch Failed
3
To Close
4
Limit Switch Open
Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
5
Second Stage Gas Valve
Energized With First
Stage
Gas Valve Off
6
Ignition Lockout
No Power Or Control
STEADY OFF
Failure
62
Red
Red
Red
LED 4
LED 2
LED 1
On
On
On
On
On
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
Off
Off
On
Off
Off
Off
On
On
On
On
On
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
Off
Off
On
Off
Off
Off
Check
Control
Pressure Switch
Venter Pressure Switch
Vent Blocked
Main Limit
AUX Limit
Gas Valve
Gas Flow
Gas Pressure
Gas Valve
Flame Sensor
24VAC or Control
Table 32: VAV Control Board Flash Codes
Flash Codes
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Loss of Communications with UCB
3 Flashes
Space Sensor Failed
4 Flashes
SAT Sensor Failed
5 Flashes
RAT Sensor Failed
6 Flashes
OAT Sensor Failed
7 Flashes
OAH Sensor Failed
8 Flashes
RAH Sensor Failed
9 Flashes
IAQ Sensor Failed
10 Flashes
OAQ Sensor Failed
11 Flashes
APS Switch Failed
12 Flashes
Limit 2 Switch Open
13 Flashes
Purge
14 Flashes
VFD Input Failure
15 Flashes
Dirty Filter Switch
16 Flashes
Econ Minimum Position Alarm
17 Flashes
Space Temp/Time Alarm
18 Flashes
Water Coil Freeze Stat Alarm
19 Flashes
SAT Alarm for Cooling
20 Flashes
SAT Alarm for Heating
Description