Checking The Outdoor System - Sanyo SAP-CMRV3143GJH Technical & Service Manual

Dc inverter multi-system air conditioner
Table of Contents

Advertisement

9-3. Checking the Outdoor System

9-3-1. Checking the outdoor unit
No.
1
• Apply 220 V AC between terminals 1 and 2 on the
outdoor unit 3P terminal block.
2
• Of the connector T-RUN/TEST terminals, short-circuit
the T-RUN terminal to the COM terminal.
NOTE: If the above check items are okay, but the outdoor unit does not operate, there may be a faulty connection between
the indoor unit and the outdoor unit.
9-3-2. Using forced defrost procedure
No.
1
• Connect a dummy resistor of 39 kΩ to the outdoor coil
temperature sensor connector.
Control
Control
Check items (unit operation)
• The LED (red) on the control circuit board must
illuminate.
• The compressor, fan motor, 4-way valve, and solenoid
valve (for the hot gas bypass) must turn ON.
(They turn ON a few seconds after the power is turned
ON.)
Check items (unit operation)
Non-stop defrost
Indoor fan
Setting
CM
Solenoid valve
(for hot gas
bypass)
OFF
Outdoor fan
ON
Defrost or
clean defrost
lamp
Defrost start
NOTE:
The dashed line for the defrost or clean defrost lamp
indicates lamp illumination at clean defrost only.
• The maximum length of defrost operation is 12
minutes.
Defrost can also be ended based on the below
conditions for the outdoor heat exchanger sensor.
Less than 2 minutes → Not ended
2 minutes or more → 10°C or higher
(However, the condition is 7°C or higher when the
outdoor air temperature is below 0°C.)
22
30 sec.
LL Stop
Stop
Stop
LL
LL
120 Hz
ON
5 sec.
ON
OFF
(ON)
End
Setting
10 sec.
OFF
ON