Specification; Set Up - Honeywell PW6K1OUT Installation Manual

Table of Contents

Advertisement

Installing the PW-6000 Output Module

Specification

Specification
The Output Board is for use in low voltage, class 2 circuits only.
Primary power
10 to 16VDC 275mA
Relay contacts
Relays 0 through 15 outputs, Form-C, 2A @ 28VDC, resistive
:
Inputs
Two unsupervised dedicated inputs
Communication
RS-485
Wire requirements
Power
RS-485
Alarm inputs
Outputs
Mechanical
Dimension
Weight
Environment
Temperature
Humidity

Set Up

Table 1: PW6000 Output Module Jumper Setting
Jumper
J1
2
:
:
:
Range 9,600 to 38,400 bps
:
1 twisted pair, 18AWG
24AWG, 4,000 feet (1,200 m) max., 2 twisted pair with shield (120
23pF) (Belden 9842 or equiv.)
1 twisted pair per input, 30 ohms max.
As required for the load
:
5.5" (140 mm) W x 9" (229 mm) L x 1" (25 mm) H
12 oz. (340 g) nominal
:
0°C to +49°C, operating, -55°C to +85°C, storage
0% to 85% RHNC
Setting
Default
OFF
*
ON
Selected
Port 1 RS-485 EOL
terminator is not active
Port 1 RS-485 EOL
terminator is active