Honeywell DT70 Series Quick Start Manual

Honeywell DT70 Series Quick Start Manual

Digital fan-coil thermostats 2-pipe fan-coil control

Advertisement

Quick Links

!"#$%&'()'&
/**2)-/")+0
The DT70 digital thermostats are designed for ON/OFF
control of the valve, or the valve and fan in 2-pipe fan-
coil applications and also one-stage compressors in
DX-type equipment.
The thermostat operates an on/off valve to provide
control at the desired setpoint temperature.
Fan-coil thermostat models are available with constant
or cycled fan operation, and have a three-speed fan
selector switch with low, medium and high settings.
The fan can also be controlled from the thermostat. In
some cases it is wired to run continuously, and can be
switched off with the system ON/OFF switch.
Heat/cool changeover operation is also possible on all
versions. This function can be accomplished by
changing the Heat/Cool parameter in SETUP mode.
!"#"$%&'(%)*+,"&'$-./0,1$%$1
2*3"3.''(%)*+,"&'+,)$/,&
*(+!,-"%&*'-).)-/")+0%&1''"
.'/",('&
Elegant styling with digital display makes
thermostat well harmonised with any interior
decoration of office or hotel
Digital display of room ambient temperature, with
display of user selected setpoint on demand
Push button adjustment of setpoint
Push button setting of Heat/Cool changeover
Switches allow manual control of system operation
and fan speed
Thermostat mounts directly onto a wall, a standard
65365mm junction box (hole pitch 60mm) or a
85385mm junction box
Ability to set minimum relay off-times (heating or
cooling) for applications requiring compressor short-
cycle protection (0~10min.)
Ability to set control-off-times for applications
requiring starting-time reservation (0~24hr.)
Ability to display temperature sensor failure for
easier troubleshooting
EEPROM permanently retains user settings in the
event of power loss
Suitable for use with Honeywell VC4000/VC6000
series and V4043/V4044 valves and compressor
starters/relays up to 2A full load rating
Application ......................................................... 1
Features ............................................................ 1
Specifications ...................................................... 2
Installation .......................................................... 3
Wiring diagram .................................................... 4~5
Operation ...........................................................
Contents
6
EN1001R0 KO06 2000

Advertisement

loading

Summary of Contents for Honeywell DT70 Series

  • Page 1 2-pipe fan- event of power loss coil applications and also one-stage compressors in • Suitable for use with Honeywell VC4000/VC6000 DX-type equipment. series and V4043/V4044 valves and compressor The thermostat operates an on/off valve to provide starters/relays up to 2A full load rating control at the desired setpoint temperature.
  • Page 2 DT70 FAN -COIL THERMOSTATS &*'-).)-/")+0& Table 1. Model selection guide Model Application Fan Operation Switches Supply voltage Cycled / On / Off 3-Speed Vac±10%, Constant (SPDT) 50/60Hz (SP3T) DT70-F002ET 2-pipe Fancoil Cycled DT70-F012ET 2-pipe Fancoil Cycled DT70-F003ET 2-pipe Fancoil+Remote control of Chiller Constant : 5~35 : 7 or 9 screw –in terminals per unit,...
  • Page 3 93:8678;%6<=%6<=>?3@656 The DT70 Series thermostat is the temperature control element The DT70 Series thermostat can be directly mounted on the in the fan-coil or air-conditioning system, and must be located wall or on either a 65x65mm standard junction box or a about 1.5m above the floor in a position with good air...
  • Page 4 DT70 FAN -COIL THERMOSTATS Wiring Diagram DT70-F002ET / F012ET RELAY CONTROL ELECTRONICS Switch OFF ON ON/OFF Switch CLOSE COOL/ HEAT Overload Protection VC6013 Device Fig. 3. DT70-F002ET, DT70-F012ET Cool-Heat-Off wiring diagram with 3-speed cycled fan. EN1001R0 KO06 2000...
  • Page 5 DT70 FAN -COIL THERMOSTATS DT70-F003ET RELAY CONTORL ELECTRONICS FAN Switch ON/OFF Switch COOL/ HEAT Over Load INTERNAL UNIT VALVE Protection (Fan-Coil) Device AUTO MANUAL HI-LO PRESSURE SWITCH COMPRESSOR MOTOR EXTERNAL UNIT (CHILLER) Fig. 4. DT70-F003ET Cool-Heat-Off wiring diagram with 3-speed fan and CHILLER. EN1001R0 KO06 2000...
  • Page 6 NOTE : During the timer counting, If the power is failed or system switch is off, the timer setting is canceled. HONEYWELL Honeywell Co., Ltd. Home and Building Control 6F, Hanil Group Building 191, Hangangro-2ga, Yongsan-gu, Seoul, 140-702, Korea Tel.