How to check the existing piping settings
You can check whether the existing piping settings are enabled.
1. Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 9)
3. Press SW01 four times to set the LED displays (D800 to D805) to the "LED displays for existing piping settings"
shown below. If the setting is enabled, D802 lights and D804 and D805 flash rapidly. (Fig. 10)
4. Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial
status.
(Fig. 9)
LED displays indicated when step 3 is taken
D800
D801
D802
D803
D804
: ON,
: OFF,
: Slow flashing
When restoring the factory defaults
To restore the factory defaults in situations such as when relocating the units, follow the steps below.
1. Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 11)
3. Press SW01 14 times to set the LED displays (D800 to D805) to the "LED displays restored to factory defaults"
shown below. (Fig. 12)
(Fig. 11)
LED displays indicated when step 2 is taken
D800
D801
D802
D803
D804
: ON,
: OFF,
: Slow flashing
4. Hold down SW02 for at least 5 seconds, and check that D804 fl ashes slowly. (Fig. 13)
5. Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 13)
LED displays indicated when step 4 is taken
D800
D801
D802
D803
D804
: ON,
: OFF,
: Slow flashing
31-EN
1131601101 EN FR ES.indb 16
1131601101 EN FR ES.indb 16
(Fig. 10)
LED displays for existing piping settings
D805
D800
D801
D802
D803
D804
: ON,
: OFF,
: Rapid flashing
(Fig. 12)
LED displays restored to factory defaults
D805
D800
D801
D802
D803
D804
: ON,
: OFF,
: Rapid flashing
D805
13

Troubleshooting

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition
to using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote
controller of the indoor unit are described in the Installation Manual of the indoor unit.
LED displays and check codes
No.
Error
D805
1
Normal
2
Discharge temperature sensor (TD) error
3
Heat exchanger temperature sensor (TE) error
4
Heat exchanger temperature sensor (TL) error
5
Outside air temperature sensor (TO) error
6
Suction temperature sensor (TS) error
7
Heat sink temperature sensor (TH) error
8
Miss-mounting of sensor (TE, TS)
9
EEPROM error
10
Compressor breakdown
11
Compressor lock
D805
12
Current detection circuit error
13
Case thermostat activated
14
Unset model type
15
Communication error between MCUs
16
Discharge temperature sensor error
17
High pressure SW error
18
Power supply voltage error
19
Heatsink overheating error
20
Gas leak detected
21
4-way valve reversal error
22
High pressure protective activated
23
Fan system error
24
Compressor driver device short circuit
25
Position detection circuit error
: ON,
: OFF,
: Rapid flashing (5 times/sec.)
LED displays
Service Switches
D800
D802
D804
SW01
SW02
D801
D803
D805
– 16 –
Display
D800
D801
D802
*
The LEDs and switches are located at
the Sub P.C. board of the outdoor unit
as shown in the fi gure on the left.
LED displays
D800
D801
D802
D803
1115284101
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (Green)
D803
D804
D805
EN
TH
D804
D805
ID
32-EN