Page 1
PSSu E S 2DO 2(-T) Decentralised system PSSuniversal I/O Operating Manual-21352-EN-07...
Page 2
We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
............................General wiring guidelines ......................6.1.1 Mechanical connection of the base modules................Terminal configuration ......................Connecting the module......................Operation ..........................Messages ..........................Display elements ........................7.2.1 Display elements for module diagnostics ................. Operating Manual PSSu E S 2DO 2(-T) 21352-EN-07...
Page 4
Contents 7.2.2 Display elements for output status.................... Technical details ........................Order reference ........................Product ............................. Accessories ..........................Operating Manual PSSu E S 2DO 2(-T) 21352-EN-07...
Introduction Validity of documentation This documentation is valid for the products PSSu E S 2DO 2 and PSSu E S 2DO 2-T. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu E S 2DO 2(-T) 21352-EN-07...
– Overload-proof LEDs for: – Switch status of each output – Module error For standard applications in system environment A and B T-type: PSSu E S 2DO 2-T: for increased environmental requirements Operating Manual PSSu E S 2DO 2(-T) 21352-EN-07...
– 2D code 3: Labelling strip for the terminal configuration on the base module 4: Status LEDs 5: Name of electronic module 6: Connection level 1 7: Connection level 2 8: Connection level 3 Operating Manual PSSu E S 2DO 2(-T) 21352-EN-07...
Page 9
11: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 12: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating Manual PSSu E S 2DO 2(-T) 21352-EN-07...
PAS4000 from Version 1.0.0 – We recommend that you always use the latest version (download from www.pilz.com). The PSSu E S 2DO 2 module may be used in conjunction with the following base modules: PSSu BP 1/8 S PSSu BP 1/8 C...
Safety The module PSSu E S 2DO 2-T may be used in conjunction with the following base mod- ules: PSSu BP 1/8 S-T PSSu BP 1/8 C-T PSSu BP-C 1/8 S-T PSSu BP-C 1/8 C-T PSSu BP 1/12 S-T PSSu BP 1/12 C-T...
The module routes the periphery supply from the module bus to the base module termin- als. The periphery supply is used to supply the outputs. Outputs The head module sets the output status via the module bus. Operating Manual PSSu E S 2DO 2(-T) | 12 21352-EN-07...
PSSu assignment in system environment B Data access is via pre-defined I/O data types: I/O data name I/O data type I/O data element Meaning O0(11), O1(21) ST_O_DO Data: BOOL Output data O0, O1 Operating Manual PSSu E S 2DO 2(-T) | 13 21352-EN-07...
5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E S 2DO 2(-T) | 14 21352-EN-07...
Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Operating Manual PSSu E S 2DO 2(-T) | 15 21352-EN-07...
This is how the base module is coded. The mechanics of the electronic modules are designed for 50 plug in/out cycles. Operating Manual PSSu E S 2DO 2(-T) | 16 21352-EN-07...
Installation 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating Manual PSSu E S 2DO 2(-T) | 17 21352-EN-07...
– The substitute values are used for the modules' FS outputs, with Valid Bits = FALSE. CAUTION! Sparking can cause interference and errors! Only change the module when the load is switched off! Operating Manual PSSu E S 2DO 2(-T) | 18 21352-EN-07...
– Insert the stripped cable into the round fixing hole [2], as far as it will go [5]. – Pull out the screwdriver [6]. – Check that the cable is firmly seated. Operating Manual PSSu E S 2DO 2(-T) | 19 21352-EN-07...
Page 20
– Inputs/outputs on the counter modules: 1.5 mm (AWG16) – Analogue inputs/outputs: 1.5 mm (AWG16) – Communication cables: 1.5 mm (AWG16) – Test pulse outputs: 1.5 mm (AWG16) – Power supply: 2.5 mm (AWG12) – Functional earth: 2.5 mm (AWG12) Operating Manual PSSu E S 2DO 2(-T) | 20 21352-EN-07...
PSSu BP 1/8 C-T 12-22: 0 V periphery supply (12-22 linked within the base module) 13-23: 0 V periphery supply (13-23 linked within the base module) 14: Not connected 24: Not connected Operating Manual PSSu E S 2DO 2(-T) | 21 21352-EN-07...
Page 22
PSSu BP-C 1/8 C-T 12-22: 0 V periphery supply (12-22 linked within the base module) 13-23: C-rail supply (13-23 linked within the base module) 14: Not connected 24: Not connected Operating Manual PSSu E S 2DO 2(-T) | 22 21352-EN-07...
Page 23
(13-23-16-26 linked within the base module) 14: Not connected 24: Not connected 15-25: 0 V periphery supply (15-25 linked within the base module) 16-26: C-rail supply (13-23-16-26 linked within the base module) Operating Manual PSSu E S 2DO 2(-T) | 23 21352-EN-07...
ST communication error Error in ST communication with Change faulty module. the head module. Bus termination error There is no end bracket. Install a terminating plate with in- tegrated end angle. Operating Manual PSSu E S 2DO 2(-T) | 25 21352-EN-07...
- - - 0 signal O0 (Out- put 0) 11 21 Green 1 signal 12 22 - - - 0 signal O1 (Out- 13 23 put 1) 14 24 Green 1 signal Operating Manual PSSu E S 2DO 2(-T) | 26 21352-EN-07...
0,000 - 2,500 A 0,000 - 2,500 A Residual current at "0" signal 0,01 mA 0,01 mA Max. transient pulsed current 12 A 12 A Max. internal voltage drop 140 mV 140 mV Operating Manual PSSu E S 2DO 2(-T) | 27 21352-EN-07...
Page 28
EN 60068-2-27 Number of shocks Acceleration Duration 11 ms 11 ms In accordance with the standard EN 60068-2-27 EN 60068-2-27 Number of shocks 1000 1000 Acceleration Duration 16 ms 16 ms Operating Manual PSSu E S 2DO 2(-T) | 28 21352-EN-07...
Page 29
12,6 mm Depth 60,2 mm 60,2 mm Weight 33 g 32 g Mechanical coding Type Colour Dark grey Dark grey Where standards are undated, the 2005-04 latest editions shall apply. Operating Manual PSSu E S 2DO 2(-T) | 29 21352-EN-07...
314 622 PSSu BP-C1 1/12 C Base module with C-rail and cage clamp terminals 312 623 PSSu BP-C1 1/12 C- Base module with C-rail and cage clamp terminals, T-type 314 623 Operating Manual PSSu E S 2DO 2(-T) | 30 21352-EN-07...
Page 31
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...