Electrical Wiring & Application Control - Haier AB072FDAHA Installation Manual

Mrv intelligent network cassette type air conditioner indoor unit
Hide thumbs Also See for AB072FDAHA:
Table of Contents

Advertisement

Electrical wiring & Application control
Warning
Electrical installation should be entrusted with qualified servicemen and done in accordance with the
installation manual. Special return circuit must be used. Insufficient capacity return circuit and
inappropriate installation may lead to fire accidents.
Specific cables should be used for the wiring. To avoid external tension of the cables, the terminals
should be firmly fixed. Inappropriate connection and fixture may lead to fire accidents.
The unit must be earthed.
The unit should be earthed properly. Poor earth may lead to shocks. The earth wire should not be
connected to gas pipes, water pipes, lightning rods or telephone wires.
Caution
Electric leak breaker should be installed. Without it, shock accidents may occur.
To avoid danger, damaged cable must be replaced by professionals of cable makers or the like. Wires
used by the indoor unit should be selected according to the installation manual.
Never connect the block terminal in the control circuit (A, B, C, P, Q, X and Y) to a 220-230V or a
380-400V power line. Otherwise, it may lead to mechanical damage or personal injury.
Avoid contact of electric wires with high temperature pipes to prevent melting of the outer isolation.
Wires should be made into a ì Uî shape after connected to the block terminal, and fixed with clips.
Controlling wires may be laid and fixed together with the refrigerant tubes.
If the supply cord is damaged,it must be replaced by the manufaturer or its service agent or a similar
qualified person.
The wiring method should be in line with the local wiring standard.
All the cables shall have got the European authentication certificate.
The breaker of the air conditioner should be all-pole switch,and the distance between its two contacts
should be no less 3mm.Such means for disconnection must be incorporation in the fixed wiring.
The power cable and connecting cable are self-provided.
Power specifications
The specifications of the power circuit are listed in the table below. Smaller capacity may cause
overheat or burnout.
Item
Indoor unit
Central controller
Power wire (L)
Manual
holding wire
power
Fuse
switch
Model
Number of
Core sec-
L 50m
cores
tional area
< 500m
AC
AB072~282
5 A /
1.5mm
2
220-
2 5 0
FDAHA
15A
H05RN-F
2
230V,
500m<
AB072~282
V
3G1.5mm
2
1000m
50Hz
AC
FDBHA
2.5mm
1) The type of connecting wire is shielded wire.The type of the power cord is H07RN-F(3G).
NOTE:
2) The wiring diagram refer to the wiring diagram on the indoor and outdoor units.
10
Connecting cable
Indoor & outdoor
Remote controller wire
communication wire
Number of
Core sec-
Number of
Core sec-
cores
tional area
cores
tional area
< 200m
0.75mm
2
< 500m
2
3
1.5mm
2
200m<
500m
1mm
2
2
Electrical wiring & Application control
Indoor power wiring
The indoor and outdoor units should use separate special power lines.
If several indoor units connect the same outdoor unit, the leak breakers and
switches of the indoor units should use the same power.
Centralized controller
communication wiring
The centralized controller communication wire are
non-polarity 2-core wires. (Fig. 1)
To prevent electromagnetic disturbance, please use shielded wires.
Remote controller wiring
The remote controller remote is polarized 3-core wires.
The grouped wire controller wire (between the indoor and indoor
units) is polarized 2-core wires. (Fig. 2)
380~400V,3N~,50Hz
outdoor power
earth
leak breaker manual switch
The shielding layer should be
junction box
connected together
communication wire
shielding layer earth
1PH,220~230V~50Hz
indoor power
leak breaker manual switch
communication wire
remote
shielding layer should be
centralized control signal wire
controller
connected together
centralized control signal wire earth
1PH,220~230V~50Hz
(centralized controller)
Wiring of indoor unit and outdoor unit
Wiring should be done according to the number of the
block terminal,inappropriate connetction may lead to error.
11
indoor unit
(
shielding
layer as isolation)
remote controller
grouped control
(shielding layer as isolation)
(shielding layer as isolation)
(shielding layer as isolation)
indoor unit
indoor unit
P
(centralized
Q
C
controller)
remote controller
Y
B
A
X
L
N
HL
HN
specially used
by the power