2. TROUBLESHOOTING
Fault
Fault description
code
IPM and control board
46
communication fault
Too high discharge
47
temperature fault
The outdoor DC
48
fan motor fault
(upper fan motor)
The outdoor DC
49
fan motor fault
(down fan motor)
The unit turn off due to
the IPM
91
board over heating
fault
Lacking of
96
refrigerant
4-way valve
97
commutation failure
fault
Possible reasons for abnormality
1.The cable between the control
board and the driver board is
connected loosely;
2.The cable between the control
board and the driver board
fails;
3.The driver board fails;
4.The control board fails.
1. The refrigerant of the unit is not
enough;
2.The refrigerant of the unit is not
enough due to that the
installation pipe is longer.
3.Throttling service fails;
4.The outdoor ambient temperature
is too high.
1.The connecting wiring of the up
DC fan motor is loose;
2.The cord of the upper DC fan
motor fails;
3.The upper DC fan motor fails;
4.The drive circuit of the upper DC
fan motor fails;
5.The outdoor fan has been
blocked.
1.
The connecting wiring of the
down DC fan motor is loose;
2.
The cord of the down DC fan
motor fails;
3. The down DC fan motor fails;
4. The drive circuit of the down DC
fan motor fails;
5. The outdoor fan has been
blocked.
1.The outdoor ambient temp. is too
high;
2. The speed of the out fan motor is
too low if the fan motor is AC fan
motor;
3.The outdoor unit is not installed in
accordance with the standard;
4.The supply power is too low.
The refrigerant of the unit is not
enough.
1.The connecting wiring of the 4-
way valve coil is loose;
2.The 4-way valve coil fails;
3.The 4-way valve fails;
4.The driver board of the 4-way
valve fails.
How to deal with
1.Reconnect the cable between
the control board and the
driver board;
2.Replace the communication
cable between the control
board and the driver board;
3.Replace the driver board;
4.Replace the control board.
1.Check the welding point to
confirm whether the unit has
leakage point, and add some
refrigerant;
2. Add some refrigerant referring
to the installation user manual;
3.Replace the throttling service
(such as capillary, expansion
valve);
4.Normally protection.
1.Reconnect the wiring of the up
DC fan motor;
2.Replace the upper DC fan motor;
3.Replace the upper DC fan motor;
4.Replace the driver board of the
fan motor;
5.Check the outdoor fan and ensure
the outdoor fan can run normally.
1. Reconnect the wiring of the
down DC fan motor;
2. Replace the down DC fan
motor;
3. Replace the down DC fan
motor;
4. Replace the driver board of
the fan motor;
5. Check the outdoor fan and
ensure the outdoor fan can run
normally.
1.
Normal protection;
2.
Check the fan capacitor, and
replace the fan capacitor if it is
failure;
3. Reinstalled the outdoor unit
refer to the installation user
manual;
4. Normal protection.
Discharge the refrigerant and
charge the refrigerant
referring to the rating label.
1. Reconnect the wiring of the
4-way valve;
2. Replace the 4-way valve coil;
3. Replace the 4-way valve;
4.Replace the driver board of the
4-way valve.