Engineering
Potentiometer and auxiliary switches
Potentiometer and auxiliary switches cannot be added in the field.

Installation

No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.

Maintenance

The actuators GLB..1E are maintenance-free.
Disposal

Technical data

Power supply (GLB1..1E)
Operating voltage (SELV/PELV) / Frequency
Power consumption running
Power consumption holding
Power supply (GLB3..1E)
Operating voltage / Frequency
Power consumption running
Power consumption holding
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
Runtime for 90° rotary angle
Actuator sound power level
1)
C-UL: Permitted only to DC 30 V ⎓
4 / 10
Siemens
Building Technologies
WARNING
The device is considered an electronics device for disposal in terms of Eu-
ropean Directive 2012/19/EU and may not be disposed of as domestic gar-
bage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations..
AC 24 V ~ ±20 % (19.2...28.8 V ~) / 50/60 Hz
DC 24...48 V ⎓ ±20 % (19.2...57.6 V ⎓)
GLB14..1E,
2.2 VA / 1.3 W
GLB16..1E
2.5 VA / 1.5 W
GLB14..1E,
0.5 W
GLB16..1E
0.7 W
AC 100...240 V ~ ±10 % (90...264 V ~) / 50/60 Hz
GLB34..1E,
6 VA / 2 W
GLB36..1E
4 VA / 1.5 W
GLB34..1E,
0.9 W
GLB36..1E
0.6 W
10 Nm
16 Nm
10 Nm
90°
95° ± 2°
150 s
28 dB(A)
1)
A6V10636202_enAP_c
2018-01-25