7.1.3 Dry mode

* temperature control range: 16---30
* temperature difference:
Control feature: send the dehumidifying signal to the outdoor system.
When Tr>Ts+2 , the compressor will be turned on, the indoor fan will operate at the set speed. When Tr is
between the Ts and Ts+2 , the outdoor system will operate at the high dehumidifying frequency for 10 minutes
and then at the low dehumidifying mode for six minutes. The indoor fan will operate at low speed.
When Tr< Ts-1.5 , the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then turned to
the low speed option.
All the frequency converses have a
* Wind speed control: Automatic:
When Tr• Ts+ 5 , high speed.
When Ts+3 dTr< Ts+5 , medium speed.
When Ts+2 dTr< Ts+3 , low speed.
When Tr<Ts+2 , light speed.
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system will be
changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3
minutes (remain at high speed for 3 minutes.) before the next switch.
Manual: When the sensor is off or Tr< Ts+3 , the manual operation can not be made. (obligatory automatic
operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
r1
1
difference.
sectioon 2(DRY)
sectioon 3(STOP)
sectioon 1
(COOL)