APPENDIX D – UPS Commissioning Certificate
Name and address of client
Postcode
UPS Unit model
At-a-glance Settings
STEP
ACTIVITY
1. Electrical Safety Tests completed and results recorded as
per TS Traffic Installation Testing Document
(667/HE/20664/000)? See section 11.1
2. 300mA RCD present in Traffic Controller?
3. TT Earth Electrode below 100ohms? See section 11.2
a. Record Value Here: _________________ Ω
4. Traffic Controller commissioned correctly? See section 11.4
5. UPS Solution start up: See section 11.5
a. Display reads 'STANDBY' when Battery Breaker
switched ON?
b. Display reads 'LINE' when UPS Supply Breaker and
Input Circuit Breaker switched ON?
c. Traffic signals remain lit as normal when Manual
Bypass Switch switched to UPS?
d. STATUS LED is solid green?
e. ALARM LED is off?
6. Battery Support testing: See section 11.6
a. Display reads 'INVERTER' when Mains Input MCB
switched OFF?
b. STATUS LED is flashing green?
c. Traffic signals remain lit as normal?
d. Display reads 'RETRAN' then 'LINE' when Mains
Input MCB switched ON?
e. Traffic signals remain lit as normal?
Name (Print) .................................................................................................
Signature .....................................................................................................
Date carried out.............................................................................................
One copy of this form to be left with the client and one copy retained by Siemens

Version

7
Last Editor
Ore Oluwatudimu
Document
UPS Solution General Handbook
Name
Copyright ã Siemens plc 2017 All Rights Reserved
Infrastructure and Mobility, Traffic Solutions
Installation address
Postcode
Alpha FXM1100
Page 76 of 76
Status
TS008468
Date
Doc. No.
Sopers Lane, Poole, Dorset
o
Alpha FXM2000
PASS/Yes
ISSUED
31/01/2017
667/HB/47750/000
BH17 7ER
o
FAIL/No

Advertisement

Table of Contents
loading

Table of Contents