Troubleshooting Tips - GE ADHL50 Owner's Manual

Hide thumbs Also See for ADHL50:
Table of Contents

Advertisement

Available languages

Available languages

Troubleshooting Tips... Before you call for service
Save time and money! Review the charts on the following pages first and you may not need to call for service.
Problem
Dehumidifier does not start
Dehumidifier does not dry the
air as it should
Dehumidifier runs too much
Frost appears on the coils
Fan noise
Water on floor
Bucket Full LED light flashing
and alarm sounds while drain
hose is connected
Bucket fills up when using
drain pump (on some models)
49-5000545 Rev. 1
Possible Cause
The dehumidifier is unplugged.
The fuse is blown/circuit breaker is
tripped.
Dehumidifier has reached its set
humidity level or bucket is full.
Bucket is not in the proper position.
Power Failure.
Did not allow enough time to remove
the moisture.
Airflow is restricted.
Dirty Filter
The Humidity Control may not be set
low enough.
Doors and windows may not be closed
tightly.
Clothes dryer may be blowing
moisure-laden air into the room.
Room temperature is too low.
Area to be dehumidified is too large.
Doors and windows are open.
Room temperature is below 41°F (5°C)
Air is moving through the
dehumidifier.
Hose connection may be loose.
Intended to use the bucket to collect
water, but a hose was attached
Drain hose not tight on fitting.
Drain hose is kinked.
Unit not in pump mode
Pump hose not installed
Water level sensor issue
What To Do
Makes sure the dehumidifier's plug is pushed completely into
the outlet.
Check the house fuse/circuit breaker box and replace the fuse
or reset the breaker.
The dehumidifier automatically turns off when either condition
occurs. Change to a lower setting or empty the bucket and
replace properly.
The bucket must be in place and securely seated for the
dehumidifier to operate.
There is a protective time delay (up to 3 minutes) to prevent
tripping of the compressor overload. For this reason, the unit
may not start normal dehumidification for 3 minutes after it
turned back on.
When first installed, allow at least 24 hours to maintain the
desired dryness.
Make sure there are no curtains, blinds or furniture blocking
the top or back of the dehumidifier. See the Choosing a
Location section.
See the Care and Cleaning section.
For drier air, press the
pad and set to a lower percent value
(%) or at the Nonstop setting for maximum dehumidification.
Check that all doors, windows and other openings are
securely closed.
Install the dehumidifier away from the dyer. The dryer should
be vented to the outside.
Moisture removal is best at higher room temperatures. Lower
room temperatures will reduce the moisture removal rate.
Models are designed to be operated at temperatures above
41°F (5°C).
The capacity of your dehumidifier may not be adequate
Close all doors and windows to the outside.
Please operate unit at temperatures above 41 F (5 C).
Frost will usually disappear within 60 minutes. Under certain
conditions, frost may appear on the coils of your dehumidifier
at temperatures above 41°F (5°C). This is normal and frost
will usually disappear within 60 minutes. See the Automatic
Defrost section.
This is normal.
Check the hose connection. See the Removing Collected
Water section.
Disconnect the hose if using a bucket to collect water. See
the Removing Collected Water section.
Check drain hose connection.
Ensure the drain hose is pointed straight down to the floor and
is not kinked in anyway.
Ensure pump is turned on and pump light is illuminated
Ensure pump hose is properly installed on back of unit
This may be caused by very humid conditions or error with
float sensor. Check unit for a P1 error code on display. If this
is present - turn off the unit, unplug unit for a few seconds,
plug back in and turn on the unit to reset sensor. If this error
continues to occur refer to warranty section for exchange
options.
9

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Aphl50Awhl50Adhl22Adhl35

Table of Contents