Capacity Control - Toshiba RAS-B05E2KVG-E Service Manual

Hide thumbs Also See for RAS-B05E2KVG-E:
Table of Contents

Advertisement

Item
3. Outdoor fan
motor control
In cooling operation
RAS-16E2AVG-E
Compressor speed
RAS-18E2AVG-E
Fan speed range
To ≥ 38°C
To ≥ 28°C
To ≥ 15°C
To
To ≥ 5.5°C
To ≥ 0°C
To ≥ 0°C
When To is abnormal
Outdoor fan speed (rpm)
Model name
f0
f1
RAS-16E2AVG-E
0
300
RAS-18E2AVG-E
0
300
The cooling or heating capacity depending on the load is
4. Capacity
control
adjusted.
According to difference between the setup value of tempera-
ture and the room temperature, the capacity is adjusted by
the compressor revolution.
Remote controller
Set temp. (Ts)
Detection of electromotive force
Detection of motor speed and rotor position
Correction value of Hz signal ≤ Operating Hz
Operation flow and applicable data, etc.
Hz < 25.2
25.2 ≤ Hz < 66.0
66.0 ≤ Hz
Hz < 27.6
27.6 ≤ Hz < 66.0
MIN
MAX
MIN
MAX
MIN
f6
fB
f8
fE
fA
f5
fA
f7
fD
f9
f3
f7
f5
f9
f7
f2
f5
f4
f7
f6
f1
f3
f3
f5
f4
f1
f2
f2
f4
f3
OFF
fB
OFF
fE
f1
f2
f3
f4
f5
300
300
360
450
300
300
360
450
Ts –Ta
Correction of Hz signal
of compressor motor winding
Inverter output change
Commutation timing change
Change of compressor speed
RAS-16E2AVG-E
Compressor speed
RAS-18E2AVG-E
MAX
Fan speed range
fE
To ≥ 10°C
fE
To ≥ 5°C
To
fB
To ≥ -3°C
f9
To ≥ -10°C
f7
To < - 10°C
f5
When To is abnormal
fE
Fan speed range
f6
f7
f8
f9
500
550
600
650
500
550
600
650
Indoor unit
Room temp. (Ta)
- 42 -
Description
In heating operation
Hz < 31.8
31.8 ≤ Hz < 60.6
MIN
MAX
MIN
MAX
f7
f8
f9
fB
fE
fE
fE
fE
fE
fE
fE
fF
fA
fB
fC
fD
700
800
900
900
700
800
900
900
1) The difference between set
temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.
2) According to the temperature
difference, the correction value of
Hz signal which determines the
compressor speed is set up.
3)
The rotating position and speed
of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.
According to the difference
4)
resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the
commutation timing are varied.
Change the compressor motor
5)
speed by outputting power to the
compressor.
* The contents of control
operation are same in cooling
operation and heating
operation
60.6 ≤ Hz
MIN
MAX
f9
fE
fE
fE
fE
fF
fE
fF
950
950
950
950