Mitsubishi Electric MXZ-2A20NA-1 Service Manual page 63

Outdoor unit inverter-controlled multi system type
Hide thumbs Also See for MXZ-2A20NA-1:
Table of Contents

Advertisement

12-3. MXZ-3A30NA -
OUTDOOR UNIT
OPERATING PROCEDURE
1. Removing the compressor
(1)Remove the screws of the top panel, and remove the top
panel.
(2)Remove the screws of the service panel, and remove the ser-
vice panel.
Recover refrigerant gas.
(3)Remove the screws of the front panel, and remove the front
panel.
(4)Remove the screws of the rear panel, and remove the rear
panel.
(5)Disconnect the compressor lead wire from terminal of
compressor (U, V, W).
(6)Disconnect the outdoor electronic control P.C. board
connectors:
CN661, CN663, CN681, CN791, CN792, CN793, CN796,
CN931, CN932
Disconnect the noise filter P.C. board connector:
CN912
(7)Remove the screws of the electrical parts, and remove the
electrical parts.
(8)Remove the propeller.
(9)Remove the screws of the separator, and remove the
separator.
(10)Remove the sound proof felt.
(11)Detach the welded parts of the compressor suction and dis-
charge pipes (Photo 4).
(12)Remove the compressor nuts and remove the compressor.
Photo 4
Suction pipe
welded part
Discharge pipe
welded part
1
Photo 1
Screws of the top panel
Screws of
the front panel
Photo 2
Screws of
the service panel
Screws of rear panel
Photo 3
Screws of the electrical parts
63
PHOTOS
Screws of
service
panel
Screws of the top panel
Screws of
the side panel