Lennox LI012CI-160P432-1 Service Manual page 53

Table of Contents

Advertisement

Malfunction
NO.
Name
Refrigerant
11
recovery
mode
Indoor
ambient
temperature
12
sensor is
open/short
circuited
Indoor
evaporator
temperature
13
sensor is
open/short
circuited
Outdoor
ambient
temperature
14
sensor is
open/short
circuited
Outdoor
condenser
temperature
15
sensor is
open/short
circuited
Outdoor
discharge
temperature
16
sensor is
open/short
circuited
Limit/
decrease
17
frequency
due to
overload
Decrease
frequency
18
due to
overcurrent
50
Display Method of Indoor Unit
Indicator Display (during
blinking, ON 0.5s and OFF
Dual-8
0.5s)
Code
Display
Operation
Cool
Heating
Indicator
Indicator
Indicator
Fo
F1
F2
F3
F4
F5
F6
F8
A/C status
Refrigerant recovery.
The Serviceman operates it
for maintenance.
During cooling and drying
operation, indoor unit operates
while other loads will stop;
during heating operation,
the complete unit will stop
operation.
AC stops operation once
reaches the setting
temperature. Cooling, drying:
internal fan motor stops
operation while other loads
stop operation; heating: AC
stop operation
During cooling and drying
operating, compressor stops
while indoor fan operates;
During heating operation,
the complete unit will stop
operation
During cooling and drying
operation, compressor stops
while indoor fan will operate;
During heating operation,
the complete unit will stop
operation.
During cooling and drying
operation, compressor will sop
after operating for about 3
mins,
while indoor fan will operate;
During heating operation, the
complete unit will stop after
operating for about 3 mins.
All loads operate normally,
while
operation frequency for
compressor is decreased
All loads operate normally,
while
operation frequency for
compressor is decreased
Service Manual
Possible Causes
Nominal cooling mode
1. Loosening or bad contact of
indoor ambient temp. sensor and
mainboard terminal.
2. Components in mainboard fell
down leads short circuit.
3. Indoor ambient temp. sensor
damaged.(check with sensor
resistance value chart)
4. Mainboard damaged.
1. Loosening or bad contact of
Indoor
evaporator temp. sensor and
mainboard terminal.
2. Components on the mainboard
fall
down leads short circuit.
3. Indoor evaporator temp. sensor
damaged.(check temp. sensor
value
chart for testing)
4. Mainboard damaged.
Outdoor temperature sensor
hasnt been connected well or
is damaged. Please check it by
referring to the resistance table for
temperature sensor)
Outdoor temperature sensor
hasnt been connected well or
is damaged. Please check it by
referring to the resistance table for
temperature sensor)
1.Outdoor temperature sensor
hasnt been connected well or is
damaged. Please check it by
referring to the resistance table for
temperature sensor)
2.The head of temperature sensor
hasnt been inserted into the copper
tube
Refer to the malfunction analysis
(overload, high temperature
resistant)
The input supply voltage is too low;
System pressure is too high and
overload
Installation and Maintenance