Lennox LI018CI-180P432 Service Manual

Lennox LI018CI-180P432 Service Manual

Refrigerant: r410a
Hide thumbs Also See for LI018CI-180P432:

Advertisement

Service Manual
Models: LI018CI-180P432 / LI018CO-180P432
LI018HI-180P432 / LI018HO-180P432
(Refrigerant
R410A)
:
Thank you for selecting LENNOX air conditioners.

Advertisement

Table of Contents
loading

Summary of Contents for Lennox LI018CI-180P432

  • Page 1 Service Manual Models: LI018CI-180P432 / LI018CO-180P432 LI018HI-180P432 / LI018HO-180P432 (Refrigerant R410A) Thank you for selecting LENNOX air conditioners.
  • Page 2: Table Of Contents

    Service Manual Table of Contents Part Ⅰ : Technical Information ............... 1 1. Summary ........................1 2. Specifications ......................2 2.1 Specification Sheet ......................2 2.2 Operation Characteristic Curve ..................4 2.3 Capacity Variation Ratio According to Temperature ............4 2.4 Noise Curve ........................
  • Page 3 Service Manual 9. Maintenance ......................36 9.1 Precautions before Maintenance ..................36 9.2 Error Code List .......................37 9.3 Troubleshooting for Main Malfunction ................40 9.4 Troubleshooting for Normal Malfunction .................55 10. Exploded View and Parts List ..............57 10.1 Indoor Unit ........................57 10.2 Outdoor Unit .........................59 11.
  • Page 4: Part Ⅰ : Technical Information

    Service Manual Part Ⅰ : Technical Information 1. Summary Indoor Unit: LI018CI-180P432 LI018HI-180P432 Outdoor Unit: LI018CO-180P432 LI018HO-180P432 Remote Controller: YAA1FB Technical Information...
  • Page 5: Specifications

    Service Manual 2. Specifications 2.1 Specification Sheet LI018CI-180P432 LI018HI-180P432 Model LI018CO-180P432 LI018HO-180P432 Y8371 Y8383 Product Code Y8372 Y8384 Rated Voltage 208/230 208/230 Power Supply Rated Frequency Phases Power Supply Mode Outdoor Outdoor Cooling Capacity(Min~Max) Btu/h 18000(3412~20472) 18000(3412~20472) Heating Capacity(Min~Max) Btu/h...
  • Page 6 Service Manual Model of Outdoor Unit LI018CO-180P432 LI018HO-180P432 Outdoor Unit Product Code Y8372 Y8384 ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR Compressor Manufacturer/Trademark CO.,LTD CO.,LTD Compressor Model QXA-B141zF030A QXA-B141zF030A Compressor Oil RB68EP RB68EP Compressor Type Rotary Rotary Compressor Locked Rotor Amp (L.R.A) Compressor RLA 12.08 12.08...
  • Page 7: Operation Characteristic Curve

    Service Manual 2.2 Operation Characteristic Curve Cooling Heating Cooling Heating Conditions Indoor:DB80°F/WB66.9°F Outdoor:DB95°F Indoor air flow:Super High Pipe length:24.6ft Conditions Indoor:DB70°F/WB60°F Outdoor:DB19.94°F/WB19.04°F Indoor air flow:Super High Pipe length:24.6ft 10 20 30 40 50 60 70 80 90 100 Compressor speed (rps) Compressor speed (rps) 2.3 Capacity Variation Ratio According to Temperature Cooling...
  • Page 8: Noise Curve

    Service Manual 2.4 Noise Curve Indoor side noise Outdoor side noise Heating Cooling Compressor frequency(Hz) Indoor fan motor rating speed 2.5 Cooling and Heating Data Sheet in Rated Frequency Cooling: Pressure of gas pipe Inlet and outlet pipe Rated cooling Compressor connecting indoor and temperature of heat...
  • Page 9: Outline Dimension Diagram

    Service Manual 3. Outline Dimension Diagram 3.1 Indoor Unit 7 3/16 Φ2 3/16 Φ2 3/16 1 1/2 7 1/2 5 1/2 Unit:inch 8 1/8 7 5/16 38 3/16 11 13/16 8 13/16 Φ2 3/4 Φ2 3/4 1 11/16 3 1/8 Technical Information...
  • Page 10: Outdoor Unit

    Service Manual 3.2 Outdoor Unit 13 3/8 15 5/8 Unit: inch Technical Information...
  • Page 11: Refrigerant System Diagram

    Service Manual 4. Refrigerant System Diagram LI018CI-180P432 / LI018CO-180P432 Outdoor unit Indoor unit Gas pipe side Valve Di s charge Heat exchanger (evaporator) Suction Accumlator Heat Compressor exchanger (condenser) Liquid pipe side Valve Electron Strainer expansion valve COOLING LI018HI-180P432 / LI018HO-180P432...
  • Page 12: Electrical Part

    Service Manual 5. Electrical Part 5.1 Wiring Diagram ● Instruction Symbol Symbol Color Symbol Symbol Color Symbol Name White Green Jumper cap Yellow Brown COMP Compressor Blue Grounding wire YEGN Yellow/Green Black Violet Orange Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model. ●...
  • Page 13 Service Manual ● Outdoor Unit LI018CO-180P432 60000700023002 LI018HO-180P432 600007000230 The above data is subject to change without notice. Please refer to the nameplate of the unit. Technical Information...
  • Page 14: Pcb Printed Diagram

    Service Manual 5.2 PCB Printed Diagram Indoor Unit ● Top view Name Interface of communication wire for indoor unit and outdoor unit 2 Interface of live wire Interface of health function neutral wire 4 Interface of neutral wire 5 Interface of fan 6 Interface of health function live wire 7 Jumper cap 8 Auto button...
  • Page 15 Service Manual Outdoor Unit ● Top view Name Compressor three phase input interface Terminal of system high pressure protection Compressor overload protection terminal Interface of temperature sensor Terminal of electronic expansion valve Terminal for low pressure protection Interface of fan 4-way valve terminal 2-way valve terminal Terminal of compressor electric heater...
  • Page 16: Function And Control

    Service Manual 6. Function and Control 6.1 Remote Controller Introduction Buttons on Remote Controller ON/OFF button - button + button MODE button H O U R ONOFF FAN button SWING button I FEEL button button SLEEP button TEMP button TIMER-ON but CLOCK button TIMER-OFF bu TURBO...
  • Page 17 Service Manual Press this button to turn on the unit. Press this button again to turn off the unit. 2. - Button Press this button to decrease set temperature. Holding it down above 2 seconds rapidly decreases set temperature. In AUTO mode, set temperature is not adjustable.
  • Page 18 Service Manual When selecting " " by remote controller or no display, temperature indicator on indoor unit displays set temperature. When selecting " " by remote controller, temperature indicator on indoor unit displays indoor ambient temperature. When selecting " " by remote controller, temperature indicator on indoor unit displays outdoor ambient temperature. Outdoor ambient temperature display may can’t be selected for some models.When indoor unit receives "...
  • Page 19 Service Manual Replacement of Batteries in Remote Controller 1.Press the back side of remote controller marked with“ of battery box along the arrow direction. 2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of “+” polar and “-“ polar are correct. 3.
  • Page 20: Brief Description Of Modes And Functions

    Service Manual 6.2 Brief Description of Modes and Functions 1.Basic function of system (1)Cooling mode (1) Under this mode, fan and swing operates at setting status. Temperature setting range is 17~32 (2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status. (2)Drying mode (1) Under this mode, fan operates at low speed and swing operates at setting status.
  • Page 21 Service Manual (8)I feel control mode After controller received I feel control signal and ambient temperature sent by remote controller, controller will work according to the ambient temperature sent by remote controller. (9)Compulsory defrosting function (1) Start up compulsory defrosting function Under ON status, set heating mode with remote controller and adjust the temperature to 60.8 F.
  • Page 22 Service Manual Outdoor Units 1. Input Parameter Compensation and Calibration (1) Check the ambient temperature compensation function Indoor ambient temperature compensation function. a. In cooling mode, the indoor ambient temperature participating in computing control = (T – ⊿ T indoor ambient temperature cooling indoor ambient temperature compensation b.
  • Page 23 Service Manual 3. Special Functions Defrosting Control ① Conditions for starting defrosting After the time for defrosting is judged to be satisfied, if the temperature for defrosting is satisfied after detections for continuous 3minutes, the defrosting operation will start. ② Conditions of finishing defrosting The defrosting operation can exit when any of the conditions below is satisfied: ③...
  • Page 24 Service Manual 1. Starting estimation: After the compressor stopped working for 180s, if T > [T (the temperature of hysteresis is 35.6ºF )], inner pipe frozen-preventing frequency-limited temperature the machine is only allowed to start for operating, otherwise it should not be started, and should be stopped to treat according to the frozen- preventing protection: Clear the trouble under the mode of power turn-off / heating, and the protection times are not counted.
  • Page 25 Service Manual 1. Frequency limited If [T ]≤T <[T ] , you should limit the frequency raising of heating overload frequency-limited temperature inner pipe heating overload frequency reducing temperature at normal speed compressor. 2. Reducing frequency at normal speed and stopping machine: If T[ ]≤T <[T...
  • Page 26 Service Manual (6)Voltage sag protection After start the compressor, if the time of DC link Voltage sag [U ] is measured to be less than t Voltage sag protection time , Sagging protection voltage the machine should be stop at once, hand on the voltage sag trouble, reboot automatically after 30 minutes. (7)Communication fault When you have not received any correct signal from the inner machine in three minutes, the machine will stop for communication fault.
  • Page 27 Service Manual (12) Starting-up Failure Protection for Compressor Stop the compressor after its starting-up fails, restart it after 20s if the fault doesnt shows, and if they are all failing for the successive start 3 times, it shall be reported as Starting-up Failure, and then restart up it after 3 min. When it still not be able to operate through carry out the above process for 5 times, it is available if press ON/OFF.
  • Page 28 Service Manual 6. Electric Heating Function of Chassis (1) When Toutdoor amb.≤32ºF , the electric heating of chassis will operate; (2) When Toutdoor amb.>35.6ºF , the electric heating of chassis will stop operation; (3)When 32ºF <Toutdoor amb.≤35.6ºF, the electric heating of chassis will keep original status. 7.
  • Page 29: Part Ⅱ : Installation And Maintenance

    Service Manual Part Ⅱ : Installation and Maintenance 7. Notes for Installation and Maintenance Safety Precautions: 10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire Important! from the manufacture or distributor. Prohibit prolong the wire by yourself.
  • Page 30 Service Manual Safety Precautions for Installing and Relocating the Unit: To ensure safety, please be mindful of the following precautions. Warnings 1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the specified refrigerant.
  • Page 31 Service Manual Main Tools for Installation and Maintenance 1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill 4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner hexagon spanner 7. Electronic leakage detector 8.
  • Page 32: Installation

    Service Manual 8. Installation 8.1 Installation Dimension Diagram Space to the wall Space to the wall At least 6 At least 6 Drainage pipe unit:inch Installation and Maintenance...
  • Page 33 Service Manual Installation procedures Start installation Preparation before installation Read the requirements select installation Prepare tools for electric connection location Select indoor unit Select outdoor unit installation location installation location Install the support of outdoor unit Install wall-mounting (select it according to the actual situation) frame, drill wall holes Connect pipes of indoor Fix outdoor unit...
  • Page 34: Installation Parts-Checking

    Service Manual 8.2 Installation Parts-checking 8.4 Requirements for Electric Connection Name Name 1. Safety Precaution Indoor unit Sealing gum (1) Must follow the electric safety regulations when installing Outdoor unit Wrapping tape the unit. Support of outdoor (2) According to the local safety regulations, use qualified Connection pipe unit power supply circuit and air switch.
  • Page 35 Service Manual in the holes. 5. Connect the Pipe of Indoor Unit (3) Fix the wall-mounting frame on the wall with tapping screws (1) Aim the pipe joint at the corresponding bellmouth.(As show (ST4.2X25TA) and then check if the frame is firmly installed by in Fig.5) pulling the frame.
  • Page 36 Service Manual 7. Connect Wire of Indoor Unit 8. Bind up Pipe (1) Open the panel, remove the screw on the wiring cover and (1) Bind up the connection pipe, power cord and drain hose then take down the cover.(As show in Fig.11) with the band.(As show in Fig.14) (2) Reserve a certain length of drain hose and power cord for installation when binding them.
  • Page 37: Installation Of Outdoor Unit

    Service Manual 8.6 Installation of Outdoor Unit Refer to the following table for wrench moment of force: 1. Fix the Support of Outdoor Unit(Select it according to Hex nut diameter(inch) Tightening torque(ft·Ibf) the actual installation situation) Φ1/4 11.10~14.75 Φ3/8 22.12~29.50 (1) Select installation location according to the house structure.
  • Page 38: Vacuum Pumping And Leak Detection

    Service Manual (3) The water outlet cant be placed in water in order to drain 8.8 Check after Installation and Test smoothly.(As show in Fig.27) Operation 1. Check after Installation Check according to the following requirement after finishing installation. The drain hose can't be fluctuant Items to be checked Possible malfunction Has the unit been...
  • Page 39: Maintenance

    Service Manual 9. Maintenance 9.1 Precautions before Maintenance There are high-capacity electrolytic capacitors on the outdoor mainboard. Thus, even the power is cut off, there is high voltage inside the capacitors and it needs more than 20min to reduce the voltage to safety value. Touching the electrolytic capacitor within 20min after cutting the power will cause electric shock.
  • Page 40: Error Code List

    Service Manual 9.2 Error Code List (Only for the mode with this function) Malfunction of detecting plate(WIFI ) Installation and Maintenance...
  • Page 41 Service Manual Complete unit Off 3s current and blink detection 13 times malfunction Off 3s Defrosting will occur in and blink heating mode.Compressor once will operate while indoor It’s the normal state (during fan will stop. blinking, ON 10s and Off 05s) Installation and Maintenance...
  • Page 42 Service Manual Installation and Maintenance...
  • Page 43: Troubleshooting For Main Malfunction

    Service Manual 9.3 Troubleshooting for Main Malfunction ●Indoor unit: 1. Malfunction of Temperature Sensor F1, F2 Main detection points: ● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted? ● Is there short circuit due to trip-over of the parts? ●...
  • Page 44 Service Manual 2. Malfunction of Blocked Protection of IDU Fan Motor H6 Main detection points: ● SmoothlyIs the control terminal of PG motor connected tightly? ● SmoothlyIs the feedback interface of PG motor connected tightly? ● The fan motor cant operate? ●...
  • Page 45 Service Manual 3. Malfunction of Protection of Jumper Cap C5 Main detection points: ● Is there jumper cap on the mainboard? ● Is the jumper cap inserted correctly and tightly? ● The jumper is broken? ● The motor is broken? ●...
  • Page 46 Service Manual 4. Communication malfunction E6 Start Cut off power supply. Check if connection line of IDU and ODU and the wire inside electric box are correctly connected. Connect the line Correct connection? according to Malfunction eliminated? wiring diagram. Main board matches Match correctly with display board? Main board of Malfunction eliminated?
  • Page 47 Service Manual 5. Malfunction of detecting plate(WIFI) JF Start check if the connection wire are correctly connected detecting Replace the plate with the same model Is malfunction eliminated Replace the mainboard with the same model The end Installation and Maintenance...
  • Page 48 Service Manual ●Outdoor unit: Key detection point "Test point NO." Test point Related elements Test value under normal condition Test 1 Between A and C Neutral wire ,live wire 160V-265V Test 2 Between B and C Neutral wire ,live wire 160V-265V Test 3 Between D and E...
  • Page 49 Service Manual 1.Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit) Main detection point: ● Detect if the voltage of L and N terminal of wiring board is between 210AC-240AC by alternating voltage meter; ● Is reactor (L) well connected? Is connection wire loosened or pull-out? Is reactor (L) damaged? Malfunction diagnosis process: Turn on the unit and wait 1 minute...
  • Page 50 Service Manual 2.IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (AP1 below is control board of outdoor unit) Main detection point: ● If control board AP1 and compressor COMP is well connected? If they are loosened? If the connection sequence is correct? ●...
  • Page 51 Service Manual Energize and switch on Use AC voltmeter If the voltage Check the supply to measure the IPM protection between terminal L voltage and voltage between occurs after the and N on wiring machine has run for terminal L and N restore it to board XT is within a period of time?
  • Page 52 Service Manual 3.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit) Main detection point: ● If the outdoor ambient temperature is in normal range; ● If the indoor and outdoor fan is running normal; ● If the radiating environment of indoor and outdoor unit is well. Malfunction diagnosis process: Anti-high temperature, overload protection...
  • Page 53 Service Manual 4.Diagnosis for failure start up malfunction (AP1 below is control board of outdoor unit) Main detection point: ● If the compressor wiring is correct? ● If the stop time of compressor is enough? ● If the compressor is damaged? ●...
  • Page 54 Service Manual 5. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit) Main detection point: ● If the system pressure is over-high? ● If the work voltage is over-low? Malfunction diagnosis process: Synchronism Synchronism after energize the unit occurred during and start it operation...
  • Page 55 Service Manual 6.Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit) Main detection point: ● If the electron expansion valve is connected well? Is the expansion valve damaged? ● If the refrigerant is leakage? ● If the overload protector is damaged? Malfunction diagnosis process: After the unit de-energized...
  • Page 56 Service Manual 7.Communication malfunction (AP1 below is control board of outdoor unit) Main detection point: ● Check if the connection wire and the built-in wiring of indoor and outdoor unit is connected well and no damaged; ● If the communication circuit of indoor mainboard is damaged? If the communication circuit of outdoor mainboard (AP1) is dam- aged Malfunction diagnosis process: Start...
  • Page 57 Service Manual 8.Diagnosis process for outdoor communication circuit Start Test voltage value with Test 10 position in diagram with voltage meter Number jumping Test voltage value with Test 13 position in diagram with voltage meter Number jumping Outdoor unit malfunction Test voltage value with Test 11 position in...
  • Page 58: Troubleshooting For Normal Malfunction

    Service Manual 9.4 Troubleshooting for Normal Malfunction 1. Air conditioner cant be started up Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Confirm whether its due to power failure. If yes, No power supply, or poor After energization, operation indicator isnt bright wait for power recovery.
  • Page 59 Service Manual 4. ODU fan motor cant operate Possible causes Discriminating method (air conditioner status) Troubleshooting Connect wires according to wiring diagram to Wrong wire connection, or poor Check the wiring status according to circuit make sure all wiring terminals are connected connection diagram firmly...
  • Page 60: Exploded View And Parts List

    Service Manual 10. Exploded View and Parts List 10.1 Indoor Unit The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
  • Page 61 Service Manual Part Code Description LI018CI-180P432 LI018HI-180P432 Product Code Y8371 Y8383 Front Panel 27230003186 27230003186 Filter Sub-Assy 11122089 11122089 Decoration board(left and right) 2019261201/2019261101 2019261201/2019261101 Front Case 2002248401 2002248401 Guide Louver 1051276501 1051276501 Axile Bush 10542036 10542036 Air Louver(Manual) 10512732...
  • Page 62: Outdoor Unit

    Service Manual 10.2 Outdoor Unit LI018CO-180P432 The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
  • Page 63 Service Manual Part Code Description LI018CO-180P432 Product Code Y8372 Front Grill 01473049 Cabinet 01433047P Axial Flow Fan 10335008 Fan Motor 1501506402 Chassis Sub-assy 01700000094P Clapboard Assy 01233153 Compressor and Fittings 00105249G Inhalation Tube Sub-assy 030010000499 Discharge Tube Sub-assy 030013000571 Valve Support Assy 01715010P Cut off Valve Assy 07130239...
  • Page 64 Service Manual LI018HO-180P432 The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
  • Page 65 Service Manual Part Code Description LI018HO-180P432 Product Code Y8384 Front Grill 01473049 Cabinet 01433047P Axial Flow Fan 10335008 Fan Motor 1501506402 Chassis Sub-assy 01700000093P Drainage hole Cap 06813401 Clapboard Assy 01233153 4-Way Valve Assy 030152000291 Compressor and Fittings 00105249G Valve Support Assy 01715010P Cut off Valve 07130239...
  • Page 66: Removal Procedure

    Service Manual 11. Removal Procedure Warning: Be sure to wait for a minimum 11.1 Removal Procedure of Indoor Unit of 20 minutes after turning off all power supplies and discharge the refrigerant NOTE: Take A1 panel for an example. completely before removal. 1.
  • Page 67 Service Manual Electric box cover 2 4. Remove electric box cover 2 and detecting plate(WIFI) Screw Remove the screws on the electric box cover 2 and detecting plate(WIFI), then remove the electric box cover 2 and Screws detecting plate(WIFI). Detecting plate (WIFI) Loosen the connection clasps between front case sub-assy and bottom case.
  • Page 68 Service Manual Indoor tube temperature s ensor Cut off the wire binder and pull out the indoor tube temperature sensor. Screw off one grounding screw. Main Remove the wiring terminals of motor and board stepping motor. Remove the electric box assy. G rounding Screw off the screws that are locking each s c rew...
  • Page 69 Service Manual G roove R ear case ass y First remove the left side of evaporator from the groove on the rear case assy. Then remove the right side from the clasp on the C lasp rear case assy. Installation and Maintenance...
  • Page 70 Service Manual Installation and Maintenance...
  • Page 71: Removal Procedure Of Outdoor Unit

    Service Manual 11.2 Removal Procedure of Outdoor Unit Warning: Be sure to wait for a minimum of 20 minutes after turning off all power supplies and discharge the refrigerant completely before removal. Steps Procedure 1. Remove big handle,valve cover and top cover big handle Remove the screw connecting the big handle and right side plate, and then remove the big handle.
  • Page 72 Service Manual Steps Procedure Remove the screws connecting the outer case with motor support, isolation plate and chassis; lift the outer case upwards; loosen the clasps of outer case with right side plate and left side plate, and then remove the outer case. outer case 3.
  • Page 73 Service Manual Steps Procedure 4. Remove axial flow blade Remove the nut fixing axial flow blade and then remove the blade. axial flow fan motor support Remove the 6 screws fixing the motor and then remove the motor. Remove the 2 screws connecting the motor support and chassis, and then loosen the stopper to remove the motor support.
  • Page 74 Service Manual Steps Procedure 6. Remove the soundproof sponge Tear off the sticking stripe and then remove the soundproof sponge. soundproof sponge 7. Remove isolation plate Remove the 2 screws connecting the isolation plate and condenser side plate; remove the 3 screws connecting the isolation plate and chassis, and then remove the isolation plate.
  • Page 75 Service Manual Steps Procedure 9. Remove compressor compressor Remove the 3 foot nuts fixing compressor and then lift the compressor upwards to remove the compressor and damping cushion. Note: Keep the ports of discharge pipe and suction pipe from foreign objects. condenser sub-assy 10.
  • Page 76: Appendix

    Service Manual Appendix: Appendix 1: Reference Sheet of Celsius and Fahrenheit Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Set temperature Fahrenheit Fahrenheit Fahrenheit display Fahrenheit display Fahrenheit display Fahrenheit Celsius (℃) Celsius (℃) Celsius (℃) temperature temperature temperature (℉)...
  • Page 77: Appendix 3: Pipe Expanding Method

    Service Manual Appendix 3: Pipe Expanding Method Pipe Note: Pipe cutter Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps: Leaning Uneven Burr A:Cut the pip ● Confirm the pipe length according to the distance of indoor unit and outdoor unit. ●...
  • Page 78: Appendix 4: List Of Resistance For Temperature Sensor

    Service Manual Appendix 4: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) -2.2 138.1 18.75 138.2 3.848 208.4 1.071 -0.4 128.6 69.8 17.93 3.711 210.2 1.039...
  • Page 79 Service Manual Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) -2.2 181.4 25.01 138.2 5.13 208.4 1.427 -0.4 171.4 69.8 23.9 4.948 210.2 1.386 162.1 71.6 22.85 141.8 4.773 1.346 153.3 73.4...
  • Page 80 Service Manual Resistance Table of Discharge Temperature Sensor for Outdoor(50K) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) Temp.( Resistance(kΩ) -20.2 853.5 120.2 18.34 190.4 4.754 -18.4 799.8 51.8 93.42 17.65 192.2 4.609 -16.6 53.6 89.07 123.8 16.99 4.469 -14.8 703.8 55.4 84.95 125.6 16.36...
  • Page 81 Visit us at www.lennox.com, or contact us at 1-877-726-0024. © 2014 Lennox Industries Inc. For a complete list of the registered and common law trademarks owned by Lennox Industries Inc., please visit www.lennox.com.