2. Infrared Sensor Shutdown Delay
This is the delay between the infrared sensor detecting ice and the start of the shutdown
sequence. The infrared sensor shutdown delay is factory-adjusted to 100 seconds and
no adjustment is required for most dispenser unit/ice storage bin applications.
a) Standard Ice Storage Bin:
When installed on a standard ice storage bin, any shutdown delay setting is acceptable.
b) Dispenser Unit:
For typical dispenser unit applications, a 100-second shutdown delay is recommended.
However, on some dispenser unit applications, the ice level at shutoff may need to be
adjusted depending on the dispenser agitation or dispense method. Should a different
shutdown delay be desired, adjust S1 dip switch 1, 2, and 3 to obtain the shutdown
delay needed. See the table below. For further details, contact Hoshizaki Technical
Support at 1-800-233-1940.
Note: When the shutdown sequence begins, the compressor de-energizes immediately
and then 5 minutes later the gear motor and fan motor de-energize.
Increasing the shutdown delay allows a higher level of ice in the dispensing unit/
storage bin before shutdown. This could lead to icemaker movement or ice overflow.
WARNING
S1 Dip Switch
NO. 1 NO. 2 NO. 3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
Shutdown Delay
0 seconds
100 seconds (1.6 minutes)
1100 seconds (18.3 minutes)
1650 seconds (27.5 minutes)
2200 seconds (36.7 minutes)
0 seconds
0 Seconds
40