Fluke FL1730-BAS User Manual page 58

Energy logger
Table of Contents

Advertisement

1730
Users Manual
Parameter
Active Power P
Apparent Power S, S fund.
Reactive Power N, Q fund.
Additional uncertainty in % of
[1]
range
[1]
Range = 1000V x Irange
Reference Conditions:
• Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
• Input Conditions: CosΦ/PF=1, Sinusoidal signal f=50/60 Hz, power supply 110V/230V ±10 %.
• Current and power specifications: Input voltage 1ph: 120V/230V or 3ph wye/delta: 230V/400V
• Input Current: I > 10 % of Irange
• Primary conductor of clamps or Rogowski coil in center position
• Temperature Coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
50
Intrinsic Uncertainty ±(% of reading + % of range)
Influence
Direct Input
Quantity
PF ≥0.99
0.5 % + 0.005 %
0.5 % + 3 x (1-PF)
0.5 <PF <0.99
+ 0.005 %
0 ≤PF ≤1
0.5 % + 0.005 %
0 ≤PF ≤1
2.5 % of measured apparent power
U >250V
0.015 %
iFlex1500-12
iFlex3000-24
150A/1500A
300A/3000A
1.2 % + 0.005 %
1.2 % + 0.0075 %
1.2 % + 7 x (1-PF)
1.2 % + 7 x (1-PF)
+ 0.005 %
+ 0.0075 %
1.2 % + 0.005 %
1.2 % + 0.0075 %
0.015 %
0.0225 %
[1]
iFlex6000-36
600/6000A
4A/40A
1.7 % + 0.0075 %
1.2 % + 0.005 %
1.7 % + 7 x (1-PF)
1.2 % + 10 x (1-PF)
+ 0.0075 %
+ 0.005 %
1.7 % + 0.0075 %
1.2 % + 0.005 %
0.0225 %
0.015 %
i40S-EL