Temperature Settings - American Water Heater 52 Series Instruction Manual

Table of Contents

Advertisement

DIFFERENTIAL SETTINGS
Adjustable user setting(s) 1°F to 20° range; factory default is 2°F.
The water heaters covered in this Instruction Manual will have 3,
6 or 9 heating elements. Each group of 3 heating elements is one
"Bank" of heating elements. Heating elements are energized in
Banks of 3. Each Bank of heating elements will have a Differential
Setting associated with it. Differential Settings are located in the
Temperatures Menu.
There is a 1st Differential Setting on all models. There will be
one additional Differential Setting visible/adjustable for each
additional Bank of (3) heating elements.
OPERATING SEQUENCE
With an Operating Set Point of 120 °F and all Differential settings
at 2 °F, the On/Off sequencing of heating element Banks would
be as follows:
DIFFERENTIAL
BANK NUMBER
SETTING
Bank 1
2°F
Bank 2
2°F
Bank 3
2°F
From the Desktop Screen, press the Operational Button underneath
"MENU" to enter the Main Menu.
Notice how the text above the Operational Buttons on the dis-
play changes as you navigate through the various menus and
screens.
With Temperatures selected (highlight in black) in the Main Menu,
press the Operational Button underneath "SELECT" to enter the
Temperatures Menu.
If Temperatures is not selected use the Up and Down buttons to
select this menu item.
With the Operating Set Point selected in the Temperatures Menu,
press the Operational Button underneath "CHANGE" to activate the
adjustment mode for this menu item.
Press the Up and Down buttons to adjust the Operating Set Point to the
desired setting.
Press the Operational Button underneath "UPDATE" to confirm the
new setting. Press the Operational Button underneath "CANCEL" to
discard the new setting and retain the previous setting.
The new Operating Set Point value should now be displayed as the
current value.
NOTE: Use this same procedure to adjust the Differential settings
and the Tank Probe Offset in the Temperatures Menu.
This same procedure is used to change user settings in other control
system menus.
TURN OFF
TURN ON TEMP
TEMP
118°F
120°F
116°F
118°F
114°F
116°F
Table 9. Changing Temperature Settings from the Desktop Screen
ACTION
TANK TEMPERATURE
Non adjustable information display. Current water temperature as
sensed by the control system from the immersion Temperature
Probe.
TANK PROBE OFFSET
User adjustable setting -5°F to +5°F range; factory default is 0°F.
If the current Tank Temperature is sensed (from the immersion
Temperature Probe) at 120°F and the offset is adjusted to -5°F the
control system would calibrate or "offset" the Tank Temperature
to 115°F. Heating cycles would then start/stop based on the
calibrated Tank Temperature.
Used to calibrate for slight differences in control system
temperature sensing. This can improve the precision of
temperature control in the storage tank and at points of use. This
feature can also be used to compensate for building recirculation
loops (hot water returning to the storage tank) that may cause
the heating cycle to terminate prematurely.

TEMPERATURE SETTINGS

The Operating Set Point and the Differential Settings are adjusted
in the Temperatures Menu. The following instructions explain how
to adjust these user settings and navigate the control system
menus.