American Water Heater 52 Series Instruction Manual page 23

Table of Contents

Advertisement

Figure 17. Control System Desktop
Menu: The left Operational Button is pressed to enter the Main
Menu where all control system menus are accessed. See Table
8 for a list of control system menus.
Icon
Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall
in response to water temperature in the storage tank as sensed from the immersion Temperature Probe.
Water temperature in the tank has reached the Operating Set Point. Shaded area of the animated ther-
mometer icon will rise and fall in response to water temperature in the storage tank as sensed from the
immersion Temperature Probe.
The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by
the control system or when either of the two Enable/Disable circuits are open circuits.
The control system is in Heating Mode and has energized the electromagnetic contactor coils for at least
one bank of heating elements. This animated icon DOES NOT indicate current has been sensed from the
heating elements, only that there is a call for heat present and the control system has initiated heating
operation.
Heating elements icon for a water heater equipped with 1 Bank of heating elements. Each circle repre-
sents one heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent
heating elements the control system has not energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 2 Banks of heating elements. Each circle repre-
sents one heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent
heating elements the control system has not energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle repre-
sents one heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent
heating elements the control system has not energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle repre-
sents one heating element. Each diagonal row of 3 elements = 1 Bank of elements. Filled circles represent
heating elements the control system has energized AND is sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle repre-
sents one heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles with an
X represent heating elements the control system has energized that it IS NOT sensing electrical current
from.
The control has detected/declared a Fault Condition. Fault message details can be viewed in the Current
Fault menu. Heating operation is discontinued (locked out) until the condition that caused the fault is cor-
rected. Power to the water heater must be cycled off and on to reset the control system.
Note: Cycling power will not reset the control system if the condition that caused the fault has not been
corrected.
The control has detected/declared an Alert Condition. The water heater will continue to operate during an
Alert Condition but there is an operational condition that requires the attention of a Qualified Service Agent.
Alert message details can be viewed in the Current Alert menu.
Help: The right Operational Button is pressed to access instructions
and explanations for user settings, Operating States, Status Icons,
manufacturer's web address, technical support phone number and
service agent contact information.
Day/Time/Operating Mode: The current time and day are also
displayed on the Desktop Screen. "Clock Not Set" will be displayed
until the time clock has been initially set. Day and Time are adjusted
in the Economy Mode Setup menu. The current Operating Mode,
either Normal Mode or Economy Mode, is displayed beneath the
day and time.
Discreet Menu Contact Information: From the Desktop Screen
press and hold down the middle (unmarked) Operational Button for
30 seconds and then release it. This will launch a discreet menu
where personalized contact information can be entered. Installing
contractors and/or service agents can enter their company name and
telephone number. This contact information will be displayed with all
Fault and Alert messages.
Table 6. Status Icons
Description
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

80 series120 series

Table of Contents